SV9000
Motor Pump Enhanced Protection Application
Page 11 (60)
Group 4, Drive Control Parameters
Code
Parameter
Range
Step
Default
Custom
Description
Page
4.1
Acc./Dec. ramp 1 shape
0—10 s
0.1 s
0
0 = Linear
>0 = S-curve acc./dec. time
28
4.2
Acc./Dec. ramp 2 shape
0—10 s
0.1 s
0
0 = Linear
>0 = S-curve acc./dec. time
28
4.3
Acceleration time 2
0.1—3000 s
0.1 s
10 s
28
4.4
Deceleration time 2
0.1—3000 s
0.1 s
10 s
28
4.5
Brake chopper
0—1
1
0
0 = Brake chopper not in use
1 = Brake chopper in use
2 = External brake chopper
28
4.6
Start function
0—1
1
0
0 = Ramp
1 = Flying start
29
4.7
Stop function
0—1
1
0
0 = Coasting
1 = Ramp
29
4.8
DC-braking current
0.15—1.5
x I
nSV9
(A)
0.1 A
0.5 x
I
nSV9
29
4.9
DC-braking time at Stop
0—250.0 s
0.1 s
0 s
0 = DC-brake is off at Stop
29
4.10
Execute freq. of DC-
brake during ramp Stop
0.1—10 Hz
0.1
Hz
1.5 Hz
30
4.11
DC-brake time at Start
0.0—25.0 s
0.1 s
0 s
0 = DC-brake is off at Start
30
4.12
Multi-step speed
reference 1
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
10 Hz
31
4.13
Multi-step speed
reference 2
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
15 Hz
31
4.14
Multi-step speed
reference 3
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
20 Hz
31
4.15
Multi-step speed
reference 4
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
25 Hz
31
4.16
Multi-step speed
reference 5
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
30 Hz
31
4.17
Multi-step speed
reference 6
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
40 Hz
31
4.18
Multi-step speed
reference 7
f
min
—f
max
(1
.
1) (1
.
2)
0.1
Hz
50 Hz
31