SV9000
Motor Pump Enhanced Protection Application
Page 25 (60)
3.4
Analog output minimum
Defines the signal minimum to be either 0 mA or 4 mA (living zero). See figure 6.2-10.
3.5
Analog output scale
Scaling factor for analog output. See figure 6.2-10.
Signal
Max value of the signal
Output frequency
Max. frequency (p. 1. 2)
Motor speed
Max. speed (n
n
x f
max
/f
n
)
Output current
2 x I
nSV9
Motor torque
2 x T
nSV9
Motor power
2 x P
nSV9
Motor voltage
100% x V
nmotor
DC-link voltage
1000 V
V
in
signal
Max V
in
3.6
Output freq. limit 1 supervision function
3.8
Output freq. limit 2 supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the output frequency goes under/over the set limit (3.7, 3.9) this function generates a
warning message via the digital output DO1 and via a relay output RO1 or RO2 depending
on the setting of parameters 12.1ó12. 6.
3.7
Output freq. limit 1 supervision value
3.9
Output freq. limit 2 supervision value
The frequency value to be supervised by the parameter 3
.
6 or 3.8). See figure 6.2-11.
I
in
signal
Max I
in
Figure 6.2-10 Analog output scale
Par. 3.5 = 50%
Par. 3.5 = 100%
Par. 3.5 = 200%
Analog
output
current
20 mA
12 mA
10 mA
Par. 3.4 = 4 mA
Par. 3.4 = 0 mA
0
50%
100%
Max. value of signal
selected by Par. 3.1