11
Installation
Instruction manual—single-phase power conditioners
IM01002005E September 2015 Eaton.com
●
●
If the Power-Sure T800R/T800P/T800F power conditioner
is overloaded, the output voltage will drop below its rated
specifications and the input fusing will open due to higher
input currents
●
●
For installation of conduit, reference NEC Article 248
and 350 and any applicable local electrical codes
Refer to the following typical wiring diagrams
for electrical hookup
2.2: Installation of hardwired models
The Power-Sure T800R/T800P/T800F hardwired models are
shipped from the factory with all available input and output
voltage selections accessible via terminal blocks for ease
of installation . It is critical to verify the source voltage prior
to making input power connections to the Power-Sure
T800R/T800P/T800F . Verify that the desired input and output
field wiring connections are made to the correct terminal
blocks, as shown for the specific model being installed .
(See Figures 2-5—page 14, 2-6—page 15, 2-7—page
16, or 2-8—page 17, depending on the model being
installed)
.
Installation
2.0: Scope
This section guides the user through installation
requirements, circuit wiring diagrams, hardwire
connections, and factory input/output configurations
for the Power-Sure T800R/T800P/T800F models .
WARNING
High voltage. Only qualified electricians should install
or perform maintenance
2.1: Installation notes
●
●
The Power-Sure T800R/T800P/T800F requires ventilation
and should not be mounted in a non-ventilated
control cabinet
●
●
After installation is complete, verify that the output
voltage is within its rated specifications
●
●
Certain loads connected to the Power-Sure T800R/T800P/
T800F with high inrush currents will cause the output
voltage to fall below usable levels if they exceed 150%
of the unit’s current rating . If high inrush currents are
expected, the Power-Sure T800R/T800P/T800F must
be oversized