16
Installation
Instruction manual—single-phase power conditioners
IM01002005E September 2015 Eaton.com
Figure 2-7: Wiring diagram 500 VA–5 kVA T800P/T800F models
Terminals
500–2500 VA
●
●
#8 stud
●
●
Maximum wire size: 10 AWG
●
●
Recommended torque: 15 lb in
3000 VA
●
●
#10 stud
●
●
Maximum wire size: 6 AWG
●
●
Recommended torque: 20 lb in
5000 VA
●
●
Wire size range: #12–1/0 AWG
●
●
Recommended torque: 45–50 lb in