19
Installation
Instruction manual—single-phase power conditioners
IM01002005E September 2015 Eaton.com
2.5: Input volts and amps specifications 8–25 kVA
Full kVA ratings may be used at 120 Vac on secondary windings (X1–N or X3–N) with exception of 20 kVA and 25 kVA units,
in which case 120 Vac loads (X1–N or X3–N) should not exceed 50% of the unit‘s rated power .
Table 2-2: Input volts and amps specifications 8–25 kVA
Power rating
Model
208 V
240 V
480 V
8 kVA
T800
a
-08000
42 A
37 A
18 A
10 kVA
T800
a
-10000
53 A
46 A
23 A
15 kVA
T800F-15000
80 A
70 A
34 A
20 kVA
T800F-20000
106 A
92 A
46 A
25 kVA
T800F-25000
132 A
115 A
57 A
a
P = wall-mounted; F = floor-mounted .
Note:
Recommended input circuit breaker should be sized 125% of stated input amperage .
Input Output
●●
208V H1–H2
●●●●●
120V X1–N
●●
240V H1–H3
●●●●●
208V X1–X2
●●
480V H1–H4
●●●●●
240V X1–X3
●
●●●●●
120V X3–N
Terminals
●●
Wire range:
10–1/0 AWG
●●
Recommended torque:
45–50 lb in
Figure 2-10: Hardwiring for 8–25 kVA units