Introduction

Instruction manual—single-phase power conditioners

   IM01002005E   September 2015  Eaton.com

1.7:   Power-Sure T800R/T800P/T800F cabinet dimensions

Table 1-1:   Cabinet standard dimensions and weights for Power-Sure T800R models

Part number

Rating  

(VA/watts)

Input

voltage

Output

voltage

Input

interface

Output

interface

Dimensions, W x D x H, in. (mm)

Weight, lb (kg)

T800R-00500

500/400

120

120

5-15P

(4) 5-20R

8.50 x 12.75 x 9.50 (215.9 x 323.9 x 241.3)

32 (15)

T800R-00700

700/500

120

120

5-15P

(4) 5-20R

8.50 x 12.75 x 9.50 (215.9 x 323.9 x 241.3)

35 (16)

T800R-00850

850/600

120

120

5-15P

(4) 5-20R

8.50 x 12.75 x 9.50 (215.9 x 323.9 x 241.3)

37 (17)

T800R-01000

1000/700

120

120

5-15P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

46 (21)

T800R-01600

1600/1200

120

120

5-15P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

62 (28)

T800R-02100

2100/1500

120

120

5-20P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

65 (29)

T800R-02500

2500/1750

120

120

5-30P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

68 (31)

T800R-03500

3500/2450

120

120/240

5-50P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

72 (33)

T800R-03501

3500/2450

208/240

120/240

6-20P

(4) 5-20R

8.50 x 12.75 x 17.50 (215.9 x 323.9 x 444.5)

73 (33)

T800R-05000

5000/3500

208/240

120/240

Hardwired

Custom 

a

15.00 x 23.75 x 22.50 (381.0 x 603.3 x 571.5)

176 (80)

T800R-07500

7500/5250

208/240

120/240

Hardwired

Custom 

a

15.00 x 23.75 x 22.50 (381.0 x 603.3 x 571.5)

210 (95)

T800R-10000

10,000/7000

208/240

120/240

Hardwired

Custom 

a

15.00 x 23.75 x 22.50 (381.0 x 603.3 x 571.5)

256 (116)

T800R-15000

15,000/10,500

208/240

120/240

Hardwired

Custom 

a

15.00 x 23.75 x 22.50 (381.0 x 603.3 x 571.5)

314 (142)

See custom output receptacles 

Figure 1-1—page 4

; 5 panels available for distribution; HW output utilizes 1 panel, other 4 panels can be used for receptacle 

interface or cabling .

Table 1-2:   Cabinet standard dimensions and weights for Power-Sure T800P models

Part number

Rating  

(VA/watts)

Input  

voltage

Output  

voltage

Input  

interface

Output 

interface

Dimensions, W x D x H, in. (mm)

Weight, lb (kg)

T800P-00500

500/500

Range 1 

ac

Range 3 

d,

Hardwired

Hardwired

9.00 x 14.00 x 10.00 (228.6 x 355.6 x 254.0)

52 (24)

T800P-00750

750/750

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

9.00 x 14.00 x 10.00 (228.6 x 355.6 x 254.0)

60 (27)

T800P-01000

1000/1000

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

9.00 x 14.00 x 10.00 (228.6 x 355.6 x 254.0)

82 (37)

T800P-01500

1500/1500

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

13.00 x 16.50 x 14.75 (330.2 x 419.1 x 374.7)

106 (48)

T800P-02000

2000/2000

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

13.00 x 16.50 x 14.75 (330.2 x 419.1 x 374.7)

125 (57)

T800P-03000

3000/3000

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

13.00 x 16.50 x 14.75 (330.2 x 419.1 x 374.7)

157 (71)

T800P-05000

5000/5000

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

27.00 x 22.50 x 28.50 (685.8 x 571.5 x 723.9)

437 (198)

T800P-08000

8000/8000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

27.00 x 22.50 x 28.50 (685.8 x 571.5 x 723.9)

495 (225)

T800P-10000

10,000/10,000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

27.00 x 22.50 x 28.50 (685.8 x 571.5 x 723.9)

537 (244)

 Range 1: 120/208/240/480 .

 Range 2: 208/240/480 .

 Input and output voltage is field configurable; units will ship from the factory configured as follows: Range 1—120 V (input/output);  

Range 2—240 V (input/output) .

 Range 3: 120/208/240 .

Table 1-3:   Cabinet standard dimensions and weights for Power-Sure T800F models 

Part number

Rating  

(VA/watts)

Input  

voltage

Output  

voltage

Input  

interface

Output  

interface

Dimensions, W x D x H, in. (mm)

Weight, lb (kg)

T800F-05000

5000/5000

Range 1 

ac

Range 3 

d

Hardwired

Hardwired

23.00 x 20.00 x 28.50 (584.2 x 508.0 x 723.9)

407 (185)

T800F-08000

8000/8000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

23.00 x 20.00 x 28.50 (584.2 x 508.0 x 723.9)

465 (211)

T800F-10000

10,000/10,000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

23.00 x 20.00 x 28.50 (584.2 x 508.0 x 723.9)

507 (230)

T800F-15000

15,000/15,000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

35.00 x 25.00 x 39.50 (889.0 x 635.0 x 1003.3) 830 (376)

T800F-20000

20,000/20,000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

35.00 x 25.00 x 39.50 (889.0 x 635.0 x 1003.3) 950 (431)

T800F-25000

25,000/25,000

Range 2 

bc

Range 3 

d

Hardwired

Hardwired

35.00 x 25.00 x 39.50 (889.0 x 635.0 x 1003.3) 1070 (485)

 Range 1: 120/208/240/480 .

 Range 2: 208/240/480 .

 Input and output voltage is field configurable; units will ship from the factory configured as follows: Range 1—120 V (input/output);  

Range 2—240 V (input/output) .

 Range 3: 120/208/240 .

Summary of Contents for T800R-00500

Page 1: ...Instruction manual single phase power conditioners Power Sure 800...

Page 2: ...ing 1 1 3 Location and storage 1 1 4 Prerequisites to installation 1 1 5 General description 1 1 6 Electrical specifications 2 1 7 Power Sure T800R T800P T800F cabinet dimensions 3 SECTION 2 INSTALLAT...

Page 3: ...VA T800R 120 Vac input and output 60 Hz 12 2 2 Wiring diagram for 1 2 5 kVA T800R 120 Vac input and output 60 Hz 12 2 3 Wiring diagram for 3 5 kVA T800R 120 Vac input and output 60 Hz 13 2 4 Wiring di...

Page 4: ...nergy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to caus...

Page 5: ...policies The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy No warranties express or implied including warranties of fitness for...

Page 6: ...________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________...

Page 7: ...e sides of the enclosure Air exhausts are at the rear of the enclosure Therefore it should be installed in a clean dry place with enough clearance to allow a free flow of air Allow at least four inche...

Page 8: ...hing unity with load power factor as poor as 0 6 Meets FAA G 201e power factor specifications Harmonic attenuation 23 dB for load reflected harmonics Galvanic isolation NEC 250 5d 001pf Surge protecti...

Page 9: ...6 x 355 6 x 254 0 52 24 T800P 00750 750 750 Range 1 ac Range 3 d Hardwired Hardwired 9 00 x 14 00 x 10 00 228 6 x 355 6 x 254 0 60 27 T800P 01000 1000 1000 Range 1 ac Range 3 d Hardwired Hardwired 9...

Page 10: ...1 5 1 5 30R 120 30 S 1 1 L5 30R 120 30 F 1 1 6 15R 208 240 15 T 1 1 L6 15R 208 240 15 G 1 2 6 15R 208 240 15 U 1 2 L6 15R 208 240 15 H 1 1 6 20R 208 240 20 V 1 1 L6 20R 208 240 20 I 1 2 6 20R 208 240...

Page 11: ...anual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 3 Cabinet standard dimensions for 1 3 5 kVA Power Sure T800R models Figure 1 4 Cabinet standard dimensions for 5 15...

Page 12: ...6 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 5 Cabinet dimensions T800P wall panel mounted unit 500 1000 VA...

Page 13: ...7 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 6 Cabinet dimensions T800P wall panel mounted unit 1500 3000 VA...

Page 14: ...8 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 7 Cabinet dimensions T800P wall panel mounted unit 5000 10 000 VA...

Page 15: ...9 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 8 Cabinet dimensions T800F floor mounted unit 5000 10 000 VA...

Page 16: ...10 Introduction Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 1 9 Cabinet dimensions T800F floor mounted unit 15 000 25 000 VA...

Page 17: ...nd output field wiring connections are made to the correct terminal blocks as shown for the specific model being installed See Figures 2 5 page 14 2 6 page 15 2 7 page 16 or 2 8 page 17 depending on t...

Page 18: ...le phase power conditioners IM01002005E September 2015 Eaton com 2 3 Wiring diagrams Figure 2 1 Wiring diagram for 500 850 VA T800R 120 Vac input and output 60 Hz Figure 2 2 Wiring diagram for 1 2 5 k...

Page 19: ...Vac load currents X1 N or X2 N should not exceed 50 of the unit s rated power 120 Vac Neither duplex receptacle should be loaded more than 14 5 A Figure 2 4 Wiring diagram for 3 5 kVA T800R 208 240 Va...

Page 20: ...14 Installation Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 2 5 Wiring diagram for 5 7 5 kVA T800R 208 240 Vac input and 120 208 240 Vac output 60 Hz...

Page 21: ...15 Installation Instruction manual single phase power conditioners IM01002005E September 2015 Eaton com Figure 2 6 Wiring diagram 10 15 kVA T800R models...

Page 22: ...2015 Eaton com Figure 2 7 Wiring diagram 500 VA 5 kVA T800P T800F models Terminals 500 2500 VA 8 stud Maximum wire size 10 AWG Recommended torque 15 lb in 3000 VA 10 stud Maximum wire size 6 AWG Recom...

Page 23: ...IM01002005E September 2015 Eaton com Figure 2 8 Wiring diagram 8 25 kVA T800P T800F models Terminals Wire size range 12 1 0 AWG Recommended torque 45 50 lb in Note Full kVA ratings may be used at 120...

Page 24: ...7 A 1 kVA T800P 01000 9 2 A 5 3 A 4 6 A 2 3 A 1 5 kVA T800P 01500 13 7 A 7 9 A 6 8 A 3 4 A 2 kVA T800P 02000 18 3 A 10 5 A 9 2 A 4 6 A 3 kVA T800P 03000 27 5 A 15 8 A 13 7 A 6 9 A 5 kVA T800a 05000 45...

Page 25: ...Input volts and amps specifications 8 25 kVA Power rating Model 208 V 240 V 480 V 8 kVA T800 a 08000 42 A 37 A 18 A 10 kVA T800 a 10000 53 A 46 A 23 A 15 kVA T800F 15000 80 A 70 A 34 A 20 kVA T800F 2...

Page 26: ...three main component types in the Power Sure T800R T800P T800F power conditioners transformer capacitors and cooling fans 1 Transformers The transformer is designed with a considerable safety margin N...

Page 27: ...___________________________________________ _____________________________________________________ _____________________________________________________ ________________________________________________...

Page 28: ...g a world that demands more With over 100 years experience in electrical power management we have the expertise to see beyond today From ground breaking products to turnkey design and engineering serv...

Reviews: