2 - 3 Wiring Precautions
2 - 3 Wiring Precautions
Before wiring, verify the label for correct model number and
options. Switch off the power while checking.
Care must be taken to ensure that maximum voltage rating
specified on the label are not exceeded.
It is recommended that power of these units to be protected by
fuses or circuit breakers rated at the minimum value possible.
All units should be installed inside a suitably grounded metal
enclosure to prevent live parts being accessible from human
hands and metal tools.
All wiring must conform to appropriate standards of good practice
and local codes and regulations. Wiring must be suitable for
voltage, current, and temperature rating of the system.
Beware not to over-tighten the terminal screws. The torque should
not exceed 1 N-m ( 8.9 Lb-in or 10.2 KgF-cm )
Unused control terminals should not be used as jumper points as
they may be internally connected, causing damage to the unit.
Verify that the ratings of the output devices and the inputs as
specified in Chapter 6 are not exceeded.
Except the thermocouple wiring, all wiring should use stranded
copper conductor with maximum gauge 18 AWG.
Before wiring, verify the label for correct model number and
options. Switch off the power while checking.
Care must be taken to ensure that maximum voltage rating
specified on the label are not exceeded.
It is recommended that power of these units to be protected by
fuses or circuit breakers rated at the minimum value possible.
All units should be installed inside a suitably grounded metal
enclosure to prevent live parts being accessible from human
hands and metal tools.
All wiring must conform to appropriate standards of good practice
and local codes and regulations. Wiring must be suitable for
voltage, current, and temperature rating of the system.
Beware not to over-tighten the terminal screws. The torque should
not exceed 1 N-m ( 8.9 Lb-in or 10.2 KgF-cm )
Unused control terminals should not be used as jumper points as
they may be internally connected, causing damage to the unit.
Verify that the ratings of the output devices and the inputs as
specified in Chapter 6 are not exceeded.
Except the thermocouple wiring, all wiring should use stranded
copper conductor with maximum gauge 18 AWG.
21
www.comoso.com
Summary of Contents for TC 24
Page 1: ...R R www comoso com...
Page 30: ...SP1 SP1 O1HY ON OFF OUT1 Action PV Dead band O1HY Time Time 30 www comoso com...
Page 31: ...Cool only control Cool only control 31 www comoso com...
Page 36: ...3 6 Ramp 3 6 Ramp 36 www comoso com...
Page 43: ...43 www comoso com...
Page 44: ...44 www comoso com...
Page 46: ...Chapter 5 Specifications Chapter 5 Specifications 46 www comoso com...
Page 47: ...47 www comoso com...
Page 48: ...Resolution Resolution 48 www comoso com...
Page 49: ...49 www comoso com...
Page 50: ...50 www comoso com...
Page 51: ...51 www comoso com...
Page 54: ...www comoso com...