27
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
6. Scroll to
OFF
or
ON
using the
and
arrows.
7. Press
Select
to enter your choice.
A--DISP
displays.
8. Press
Back
once to return to the sub-menu or twice
to exit the program.
4.1.2.2.14 Buzzer Parameters (BUZZER)
This is the top level menu for setting the various buzzer
(audible alarm) parameters. Pressing
Select
at this menu
item provides a set of sub-menus to navigate through the
individual parameters.
4.1.2.2.14.1 Buzzer (BUZZER/B-ON/OFF)
Selects how the buzzer (audible alarm) is activated.
Selections are
OFF
,
ON ALARM
,
ON TRIP
,
ON ANY
. The
default is
OFF
.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to
BUZZER
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
B--ON/OFF
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Scroll to the selection desired,
OFF
,
ON ALARM
,
ON
TRIP
, or
ON ANY
, using the
and
arrows.
7. Press
Select
to enter your choice.
B--ON/OFF
dis-
plays.
8. Press
Back
once to return to the sub-menu or twice
to exit the program.
4.1.2.2.14.2 Buzzer Tone (BUZZER-TONE)
Selects whether the buzzer tone is
INTERMITTENT
or
STEADY
. The default is
INTERMITTENT
, which is more
likely to be heard in noisy environments.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to
BUZZER
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
B--TONE
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Scroll to the selection desired,
STEADY
or
INTRMTNT
,
using the
and
arrows.
7. Press
Select
to enter your choice.
B--TONE
displays.
8. Press
Back
once to return to the sub-menu or twice
to exit the program.
4.1.2.2.15 Trip Parameters (TRIP)
This is the top level menu for setting the various trip param-
eters. Pressing
Select
at this menu item provides a set of
sub-menus to navigate through the individual parameters.
4.1.2.2.15.1 Trip Setpoint (TRIP/T-SETPNT)
Selects the setpoint where the Trip activates due to an over-
temperature condition, or disables the Trip for over-tempera-
ture. The range is
0-250° C
. The default is
210° C
.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to
TRIP
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
T--SETPNT
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Enter the trip setpoint temperature desired, using the
and
arrows.
7. Press
Select
to enter your choice.
T--SETPNT
dis-
plays.
8. Press
Back
once to return to the sub-menu or twice
to exit the program.
4.1.2.2.15.2 Trip Dead Band (TRIP/D-BAND)
Sets hysteresis for Trip Relay deactivation on return from an
over-temperature condition. The range is
5-20° C
. The default
is
5° C
.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to
TRIP
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
T--DBAND
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Enter the trip dead band value desired, using the
and
arrows.
7. Press
Select
to enter your choice. T
--DBAND
dis-
plays.
8. Press
Back
once to return to the sub-menu or twice
to exit the program.