39
In HE Mode
Line (green) LED is on.
Code: E063
The UPS is on bypass while
operating on the High
Efficiency setting.
The equipment transferred
to bypass utility power as a
normal function of High
Efficiency operation.
Battery mode is available
and your equipment is
protected.
Site Wiring Fault
Fault (Red) LED is flash
1beep every 1 second
Code: A004
Site Fault detection is
supported on all models
anytime there is a Grounding
Neutral connection.
Alarm triggers when the
difference between ground and
neutral voltage is > 15v.
Site Fault detection should
be enabled by default. It
can still be enabled /
disabled from the LCD
settings menu.
Reconnect all input wires.
Back feed
Fault (Red) LED is On.
Beep continuous.
Code: F093
UPS has a unexpected bypass
current on battery mode
Transfer to maintenance
bypass and call service.
Inv Overload Fault
Fault (Red) LED is On
Beep continuous.
Code: F042
UPS has transferred to bypass
or fault mode because of
overload in inverter mode
The UPS transfers to
Battery mode if supporting
the load.
Remove some of the
equipment from the UPS
Byp Overload Fault
Fault (Red) LED is On.
Beep continuous.
Code: F043
UPS has cut off the output and
transferred to fault mode
because of overload in bypass
mode or HE mode.
Remove some of the
equipment from the UPS
Output Short Circuit
Fault (Red) LED is On.
Beep continuous.
Code: F031
Indicates that the UPS has
detected abnormally low
impedance placed on its
output and considers it a short
circuit
Remove all the loads. Turn
off the UPS.
Check if UPS output and
loads is short circuit.
Ensure short circuit is
removed before turning on
again.
Fan Failure
Fault (Red) LED is flash
1 beep every 1 second
Code: A085
Indicates that the fan could not
work normally
Check fans of UPS
Summary of Contents for Tower 10K
Page 1: ...Eaton 9E IN User Manual Tower 6 10K...
Page 9: ...3 2 Presentation 2 1 Front panel Tower model Tower UPS 6KS 10KS Tower UPS 6K 10K Tower EBM...
Page 11: ...5 2 3 Circuit diagram...
Page 34: ...28...
Page 36: ...30...