41
Battery Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F016
Indicates that the battery
voltage is too high
The UPS will turn off the
charger until the battery
voltage is normal
Negative power Fault
Fault (Red) LED is On.
Beep continuous.
Code: F0E1
In parallel system
,
power of
UPS is negative
Redundancy mode
,
the
fault UPS turn to fault
mode without output
Increase mode
,
UPS1&
UPS2 turn to fault mode
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: F0E2
In parallel system
,
parallel
cable disconnect
Disconnect parallel cable
one turn to fault mode
Parallel system battery
status
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E6
UPS1 connect battery
,
UPS2
without battery
Check battery connect
status
Line input different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E7
Parallel system
,
UPS1 line ok
,
UPS2 line loss
Check the line input
Power strategy different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E9
Parallel system
,
UPS mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep
OP mode be the same
Rate power different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EA
Parallel system rate power
different
Rate power different
,
not
allow turn on UPS. Keep
rate power be the same
HE in parallel
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EB
Parallel system
,
UPS mode set
as HE
HE not allow in parallel
system
,
change UPS mode
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm.
Check the alarm condition and perform the applicable action to resolve the
condition. If the alarm status changes or press the ESC button 3s on the front
panel display, the alarm beeps again, overriding the previous alarm silencing.