30
Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03
Table 16. Alarm Conditions (Continued)
Conditions
Possible cause
Action
The UPS does not start
The input source is not connected
correctly.
Check the input and battery connections.
The Remote Power Off (RPO) switch is
active or the RPO connector is missing.
If the UPS Status menu displays the "Remote
Power Off" notice, deactivate the RPO input.
77..22
D
Deettaaiill A
Allaarrm
m oorr FFaauulltt C
Cooddee
Table 17. Alarm Codes
Alarm Code
Message
Description
#004
UPS TEMP. ALARM
Ambient or NTC temperature is high
#110
BUILDING ALARM
Building alarm
#604
BATTERY LOW
Battery level is below Remaining
Capacity Limit threshold or Run Time
to Empty is below Remaining Time
Limit threshold.
#802
IMMINENT SHUTOFF
Shut down imminent
#806
EMERGENCY OFF
Emergency stop was proceed
#808
OVLD PREALARM
The load percent is > the overload
level setting(default 105%)
Table 18. Alarm Fault Codes
Fault Code
Message
Description
#007
FAN FAULT
Ventilator fault
#60D
NO BATTERY
Battery not present
#607
BATTERY FAULT
Battery need replacement OR is
faulty
#004
UPS TEMP. FAULT
UPS internal temperature is high,
over fault point
#808
POWER OVERLOAD
Overload counter time reach,
transfer to Fault mode
#805
OUTPUT SHORTED
Short circuit on output
#107
INPUT BAD WIRING
Site wiring fault that can come of
Phase neutral inversion on single
phase UPS
#809
INDU OVERLOAD
Inductive overload occurred, transfer
to Fault mode
#80A
CAPA OVERLOAD
Capacitive overload occurred,
transfer to Fault mode
#804
IMBALANCE LOAD
Load is unbalance
Summary of Contents for Tripp Lite Series SmartPro Series
Page 12: ...6 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Rear panel...
Page 26: ...20 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Display Functions...
Page 38: ...32 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Service and Support...
Page 44: ...614 4019403 614 40194 03...