18
Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03
44..33
D
Diissppllaayy FFuunnccttiioonnss
Press the Enter ( ) button to activate the menu options. Use the two middle buttons (
and
) to scroll through
the menu structure. Press the Enter (
) button to select an option. Press the (
ESC
) button to cancel or return
to the previous menu.
Table 15. Menu Map for Display Functions
Main menu
Submenu
Display information or Menu function
CONTROL
BATTERY TEST
Starts a manual battery test(possible if load>10% and battery
>80%).
RESET FAULT ST
Reset fault state.
CLEAR EVENT LOG
Clears the faults and events stored.
RESET KWH USED
Reset the power used.
FACTORY SETT
Restore factory settings.
LOCAL SETTING
LANGUAGE
Sets product general parameters, see
AUDIBLE ALARM
Sets input and output parameters, see
IN/OUT SETTING
OUTPUT VOLTAGE
Select output voltage through this submenu.
INPUT THRESHOLD
Input threshold can be set to normal or extended through this
menu.
SENSITIVITY
Sensitivity can be set to high or low through this menu.
OVRLOAD PREALARM
Overload pre-alarm can be set through this menu.
ON/OFF SETTING
COLD START
Cold start can be enabled or disabled through this menu.
AUTO RESTART
Auto restart can be enabled or disabled through this menu.
AUTO START
Auto start can be enabled or disabled through this menu.
SLEEP MODE
Sleep mode can be enabled or disabled through this menu.
SITE WIRING FLT
Site wiring fault can be enabled or disabled through this
menu.
BATTERY SETTING
AUTO BAT TEST
Auto battery test period can be set through this menu.
RESTART LEVEL
Restart battery level can be set through this menu.
BAT LOW LEVEL
Battery low percentage can be set through this menu.
BAT LOW TIME
Battery low remaining time can be set through this menu.
COM SETTING
REMOTE ON/OFF
Select input signal function for REMOTE ON/OFF.
REMOTE PWR OFF
Select input signal function for REMOTE PWR OFF.
INPUT DB9-4
Select input signal function for INPUT DB9-4.
OUTPUT RELAY
Select output signal function for OUTPUT RELAY.
OUTPUT DB9-1
Select output signal function for OUTPUT DB9-1.
Summary of Contents for Tripp Lite Series SmartPro Series
Page 12: ...6 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Rear panel...
Page 26: ...20 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Display Functions...
Page 38: ...32 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Service and Support...
Page 44: ...614 4019403 614 40194 03...