Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03
35
88..55
EElleeccttrriiccaall IInnppuutt C
Coonnnneeccttiioonnss
Catalog Number
Input connection
Input cable
SMART750RMXL2U
SMART750RMXL2UN
Fixed
NEMA 5-15P
SMART1000RMXL2U
SMART1000RMX2UN
NEMA 5-15P
SMART1500RMXL2U
SMART1500RMXLN
NEMA 5-15P
SMART2200RM2U
SMART2200RM2UN
SMART2200RMXL2U
SMART2200RMXLN
NEMA 5-20P
SMART3000RM2U
SMART3000RM2UN
SMART3000RMXL2U
SMART3000RMXLN
NEMA L5-30P
88..66
EElleeccttrriiccaall O
Ouuttppuutt
All models
Normal mode
Battery mode
Voltage regulation
Boost : Vin*1.15
Buck : Vin*0.87
(-10% ,6%)
Efficiency
>96%
750-2200 > 82%
3000 > 85%
Frequency regulation
+/-0.1 Hz
Nominal output
100/110/120/125V
Frequency
Follows input frequency
50/60Hz
Output overload
[105%,120%] 30min
[120%,150%] 5min
>150% 10s
[105% ~110%] 10s
- Output short-circuit current max RMS & delay
time: 114.5A/100ms; The max peak value: 202A
Short circuit current limitation in
battery mode
Model
Current limitation
750
41A
1000
41A
1500
56A
2200
66A
3000
90A
Transfer time
Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
Summary of Contents for Tripp Lite Series SmartPro Series
Page 12: ...6 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Rear panel...
Page 26: ...20 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Display Functions...
Page 38: ...32 Eaton Tripp Lite Series SmartPro User Guide 614 40194 Rev 03 Service and Support...