Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01
31
2.
In the
“Main Menu Screen”
press the
or
button until the “IN / OUT SETTINGS” menu is displayed.
3.
Press the
button. Use the
or
arrow buttons to display “HIGH EFFIC. MODE”.
4.
Press the
button and change the setting to “ENABLED”.
5.
The UPS transfers to High Efficiency mode after 5 minutes.
44..77
C
Coonnffiigguurriinngg tthhee B
Baatttteerryy S
Seettttiinnggss
A
Auuttoom
maattiicc B
Baatttteerryy TTeessttss
Automatic battery tests are once a month in constant charging mode.
The tests frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under load.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than
the setting capacity threshold (0 % by default). This threshold can be modified.
Restart battery level
This setting is used to define the battery restart level. The battery level must reach this threshold (0 % by
default) to enable UPS start.
See the
section to modify these settings.
44..88
R
Reettrriieevviinngg tthhee EEvveenntt LLoogg
To retrieve the Event log through the display:
1.
From the
“
“
press the
button to enter into the
”
screen .
2.
In the
“
press the
or
button until the “Event Log” menu is displayed.
3.
Press the
button. Use the
or
arrow buttons to display the events.
The log retains 50 events with the most recent event listed as the first event. Press the ESC button twice to
exit back to the
“
menu.
Summary of Contents for Tripp Lite SmartOnline Series
Page 12: ...6 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Rear Panels...
Page 38: ...32 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Retrieving the Event Log...
Page 48: ...42 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Service and Support...
Page 54: ...614 2132501 614 21325 01...