Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01
39
Table 9. UPS Fault Codes (Continued)
Fault Code
Displayed Alarm
Potential Cause
305
RECT FAULT
Hardware fault in the rectifier /PFC
308
DC BUS SHORTED
Dc bus short circuit
400
DCDC FAULT
Hardware fault in the DCDC part
500
CHARGER FAULT
Charger internal failure
502
MAX CHARGER VOLT
Recharge battery voltage is too high
503
MIN CHARGER VOLT
If battery voltage has not reached UchargeEnd
within tchargeMax then go to Float mode.
In that case if battery voltage is < 2.25 VPC then
“Charger fault” alarm is set.
tchargeMax = 24h x Number of EBM
607
BATTERY FAULT
Battery need replacement OR is faulty
700
CURRENT LIMIT
Current limitation (due to limitation, UPS has
transfered to bypass or stop)
706
UPS TEMP. FAULT
UPS internal temperature is high (due to
temperature, UPS has transfered to bypass or
stop)
70C
MIN INV VOLT
Inverter voltage is too low
70D
MAX INV VOLT
Inverter voltage is too high
805
OUTPUT SHORTED
short circuit on output
808
INV OVERLOAD
Inverter overload
Max (P,S) > L2 (L2 = 102%) max counter reached
C39
NVM NO RESPONSE
EEPROM can’t read/write normally
815
CALIBRATION FLT
DC offset of INV voltage is too high
00F
MODEL ERROR
ATE set country error(stored in COM board
EEPROM).
Table 10. UPS Alarm Codes
Alarm Code
Displayed Alarm
Potential Cause
Action
001
AC LOSS
Main AC is below charger
level
Check AC mains
004
AMB. TEMP. ALARM
Ambient temperature is high
Please check ambient temperature and if
the ventilation is blocked
104
AC FREQ NOT OK
Frequency out of range
Check AC Freq
106
AC VOLT NOT OK
Voltage out of range
Check AC Volt
Summary of Contents for Tripp Lite SmartOnline Series
Page 12: ...6 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Rear Panels...
Page 38: ...32 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Retrieving the Event Log...
Page 48: ...42 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Service and Support...
Page 54: ...614 2132501 614 21325 01...