Tripp Lite by Eaton SmartPro Advanced User Guide 614-40195—Rev 01
Table 21. RPO Connections Detail
RPO
Comments
Connector type
Terminal, 14 AWG Maximum wires
Terminal rating
60 V DC/30 V AC 20 mA max
R
Reem
moottee O
Onn//O
Offff ((R
RO
OO
O))
•
Remote On/Off allows remote action of button to switch On/Off the UPS.
•
When contact changes from open to closed, the UPS is switched-on (or stays On).
•
When contact changes from closed to open, the UPS is switched-off (or stays Off).
•
On/Off control via button has priority over the remote control.
The ROO function is only active after the first use of the "Remote OFF" function.
ROO
Comments
Connector type
Terminal, 14 AWG Maximum wires
Terminal rating
60 V DC/30 V AC 20 mA max
R
Reem
moottee ccoonnttrrooll ccoonnnneeccttiioonn aanndd tteesstt
1.
Check the UPS is shut down and the electrical supply network disconnected.
2.
Remove RPO connector from the UPS by removing the screws.
3.
Connect a normally closed volt-free contact between the two pins of connector.
Contact open: shut down of UPS.
To return to normal operation, deactivate the external remote
shut down contact and restart the UPS from the front panel.
Summary of Contents for Tripp Lite SmartPro Series
Page 6: ......
Page 10: ...x Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Figures...
Page 12: ...xii Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Tables...
Page 16: ...4 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Introduction...
Page 28: ...16 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Installation...
Page 44: ...32 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Operation...
Page 58: ...614 4019501 614 40195 01...