Tripp Lite by Eaton SmartPro Advanced User Guide 614-40195—Rev 01
Table 25. Alarm Conditions (Continued)
Conditions
Possible cause
Action
LED is On.
Beep continuous
The UPS does not provide the
expected backup time.
The batteries need charging or service.
Apply utility power for 48 hours to charge the
batteries. If the condition persists, contact your
service representative.
Power Overload
LED is On
Power requirements exceed the UPS
capacity (greater than 100% of nominal;
see
for specific output
overload ranges).
Remove some of the equipment from the UPS.
The UPS continues to operate, but may shut down
if the load increases. The alarm resets when the
condition becomes inactive.
UPS overtemperature
LED is On
1 beep every 3 seconds
The UPS internal temperature is too high
or a fan has failed. At the warning level,
the UPS generates the alarm but remains
in the current operating state. If the
temperature rises another 10°C, the UPS
shuts down.
Clear vents and remove any heat sources. Allow
the UPS to cool. Ensure the airflow around the
UPS is not restricted. Restart the UPS. If the
condition continues to persist, contact your
service representative.
The UPS does not start
The input source is not connected
correctly.
Check the input and battery connections.
The Remote Power Off (RPO) switch is
active or the RPO connector is missing.
If the UPS Status menu displays the "Remote
Power Off" notice, deactivate the RPO input.
77..22
A
Allaarrm
m oorr FFaauulltt C
Cooddeess
Table 26. Alarm Codes
Alarm Code
Message
Description
#004
UPS TEMP. ALARM
Ambient or NTC temperature is high
#110
BUILDING ALARM
Building alarm
#604
BATTERY LOW
Battery level is below Remaining Capacity Limit
threshold or Run Time to Empty is below
Remaining Time Limit threshold.
#802
IMMINENT SHUTOFF
Shut down imminent
#806
EMERGENCY OFF
Emergency stop was proceed
#808
OVLD PREALARM
The load percent is > the overload level setting
(default 105%)
Table 27. Alarm Fault Codes
Fault Code
Message
Description
#007
FAN FAULT
Ventilator fault
#60D
NO BATTERY
Battery not present
Summary of Contents for Tripp Lite SmartPro Series
Page 6: ......
Page 10: ...x Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Figures...
Page 12: ...xii Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Tables...
Page 16: ...4 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Introduction...
Page 28: ...16 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Installation...
Page 44: ...32 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Operation...
Page 58: ...614 4019501 614 40195 01...