After connecting the busbars, put the top metal
sheet onto its place.
Cable up to 240mm² cross section can be connected
easily. Start from L1 Phase.
Remove the bottom sheet completely.
Use the default connection equipment M8x20mm
bolts to connect U-earthing coppers. Connect the
earthing cable to the first and the last switchgear's
earthing bar.
Ulusoy HMH24-02 Transformer Protection Switchgear (LBS Compound Fuse)
September 2020 www.eaton.com
9
Busbar connection
Firstly put the fuse into the lower contact of L1.
Secondly, place the upper contact.
1
2