e)
Request Normal
If active the UPS transfers to inverter operation if not prohibited by EPO or alarm condition.
f)
Force Bypass
If active the UPS is forced to static bypass operation regardless of the bypass status.
g)
External Battery Breaker Status
If active the UPS knows that the batteries are disconnected.
h)
Building alarm 1-6
These can be activated separately or at the same time with other building alarms.
i)
Not in use (default)
j)
Shutdown
If active the UPS will shutdown immediately.
k)
Delayed Shutdown
If active the UPS will shutdown after user configurable delay time. Restart initiated
immediately when inactive.
l)
Normal/Bypass
If active the UPS transfers to bypass if ok. If inactive the UPS transfers to inverter when
possible.
XSlot communication
XSlot modules allow the UPS to communicate in a variety of networking environments and
with different types of devices. The UPS incorporates two (2) empty XSlot communication bays.