4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
SKU CG-S 4x1,5A
Fuses
On the front panel of the change-over module there are
O
O
per circuit
O
O
2 output fuses 2,5 AT / 250 V.
The nominal current should not exceed 3 A per circuit!
Fuse dimensions: 6.3 mm x 32 mm, sand filled.
Order no.: 400 71 070 716 / 10 qty./unit
Indicators
O
O
ON LED
The LED lights up when the voltage is present at the output
terminals.
O
O
Fault LED
The LED lights up when one or more luminaires are faulty.
Operation elements
O
O
Service-PIN
Beside the „Service“ lable there is a button which must be
operated when the system´s basic program is loaded. The
basic programming occurs factory made.
1
)
Additional features
O
O
Mixed operation of
maintained light, non-maintained light and switched
maintained light in one circuit by using of CEAG EVGs/modules
with CG-S marking can be programmed without any additional
data cable.
O
O
Individual monitoring of
up to 20 luminaires per circuit.
O
O
Easy access to fuses
O
O
Connected rating per circuit
330 W
O
O
Inrush current per circuit
60 A per circuit / 240 A per module
Example: For two circuits => 120 A per circuit
For four circuits => 60 A per circuit
O
O
Typical change-over time
AC on DC = 450 ms
Components for circuit change-over module
SKU CG-S 4x1,5A
O
O
(4 circuits each 1,5 A rated current)
O
O
The current module is connected to the controller via the BUS.
O
O
At the device configuration an address is allocated via the
controller. This occures factory made.
O
O
All functions as switching mode, monitoring function can be
programmed via the controller.
O
O
Will the circuit change over module be refitted or replaced
the programming must be changed.
ATTENTION!
Only fuses approved by CEAG
Notlichtsysteme GmbH are permit-
ted to use.
1
2
3
4
1
2
3
4