8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
If the main screen displays the
message “Insulation failure” then
fault locating can be initiated with
this menu option.
8.4.2 Menu 2: “Block & reset alarms”
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 2
Block device
Release device
Manual reset
Reset deep discharge
Reset ISO-failure
ISO-failuresearch
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: cancel
and return to
the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
<ok>
Menu 2.1:
(Menu 2.4: only directly at the station)
<ok> initiates the function:
Following a “Deep discharge protection”
message in the main screen, the mes-
sage is acknowledged with this menu
option.
(Menu 2.3: only directly at the station)
<ok> initiates the function if this ope-
ration has been activated in the menu
option «Basic settings»:
Following a mains power failure, normal
operation will not be resumed automati-
cally when mains power is restored if
the “Manual reset (On)” option has been
Block device
Release device
Manual reset
Reset deep
discharge
(Menu 2.5: only directly at the station)
<ok>
Block device
Release device
Manual reset
Reset deep
discharge
Release device
Manual reset
Reset deep
discharge
Reset ISO-failure
Block device
Release device
Manual reset
Reset deep
discharge
This device
all devices
Device address 01
Device name
Block device
Release device
Manual reset
Reset deep
discharge
<ok> initiates the function:
The selected stations will be swich-
ted free and restart operation.
activated (menu «Basic settings/
Manual reset»).
This guarantees that the emer-
gency lighting remains on until it is
ensured that the general lighting
has been switched on again, e.g. in
a cinema.
Find ISO failure
this device
all devices 01
cancel search
<ok>
Menü 2.6:
Manual reset
Reset deep
discharge
Reset ISO-failure
ISO-failuresearch
Selection with the buttons bet-
ween the displayed options.
Selection of a ZB-S system with
Device address referes to search
results in the substation setup
menu 3 «Basic settings»
Selecection of cursor position with
<ok> starts the ISO failure search
<Menu>Cancel and back to menu 2
<ok>
Menu 2.2:
This device
all devices
Device address 01
Device name
If a reset happens, the controller of
the station ZB-S returns to a normal
operation, if no further failure mes-
sages occur.
<ok> initiates the function:
All functions are cancelled;
all outputs will be isolated!
In case of mains failure occures no
battery operation.
These must be additionally separa-
ted on all poles before maintenance
work in end circuits. (see 10.3 Enab-
ling of end circuits with maintenance
work)
During the search all stations be
switched to blocked conditions!
The controller returns to normal
operation provided there are no
further fault messages.
Following a “Deep discharge
protection” message in the main
screen, the batteries must be test-
ed and replaced if necessary.
Divergent to SKU CG-S 2x3 A, with the SKU CG-S 4x1.5 A and
SOU CG-S 2x4A only one isolation fault is registered for all
circuits of the module. Limitation of the isolation fault must
be implemented at the module by enabling the single circuits.