8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Setting the system time (current date and
time) for the internal clock of the CU CG-S
control module.
ZB-S autosync:
program to „yes“ only at one station of a
group All other stations are synchronised
daily via this.
Use the
keys to toggle between
“Language: National language”
2
)
and “Language: english”
Finish and return to Menu 3 with
<Menu>
2
) Can only be selected when memory
card is inserted.
Setting the start (date and time) of the
first function test and the intervals (1 to
14 days) of subsequent function tests
(factory setting: all 7 days).
Setting the start-up time of the FT in 5s
steps (factory setting: 300s)
For all luminaires with “End of line” cut
off (EoL).
8.4.3 Menu 3: “Basic settings”
<ok> The currently selected
Menu 3.1: language is displayed
1
)
1
) Setting on delivery/initial commission-
ing
<ok>
Menu 3.2:
<ok>
Menu 3.3:
Language
Date & time
Functiontest
Durationtest
etc....
Language
Date & time
Functiontest
Durationtest
etc....
Language
Date & time
Functiontest
Durationtest
etc....
Important NOTE
These settings are the basis for all
log book entries and (synchronised)
test of the system!
If the ZB-S Systems is more than
30 days out of operation, the time
should be controlled
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & time
Functiontest
Durationtest
Delay time mains
return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Charger setup
Printer setup
Relay module setup
Webserver setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Date & Time
We 11.01.12 12:00
ZB-S autosync.: yes
F-Test Date&Time
We 11.12.07 12:00
FT start-up time 300s
Interval in days: 07
NOTE
Fall back language for controller re-
set or after the installation of a new
CU CG-S is allways english
Select the date and time positions
with
Change with
Finish with <Menu>
This request follows:
Enter “OK” synchronises the clock
of all connected substations in one
group
Substation
synchronise ?
Menu = no OK = yes
Substation
synchronise ?
Menu = no OK = yes
Select the input position for date,
time, intervals (in days) and FT start-up
time (in 5s) with
Change with
Finish with <Menu>
This request follows: