10
Instruction Booklet
IB02201004E
Effective October 2017
Revision #4
Instructions for installation, operation, and
maintenance of 38 kV type VacClad-W,
150 BIL switchgear indoor housings
EATON
www.eaton.com
3 . From the floor or from the portable lifter, roll the transformer
drawer into the auxiliary compartment until the drawer
latches into place . An audible “clicking” noise can be heard
when the drawer latches in place . Pull back on the drawer to
confirm it is fixed and latched in place . In this position, the
drawer and transformer(s) are considered in the Disconnect
position (see Figure 7) .
4 . Verify the primary shutters remain closed (see Figure 7) .
Figure 8. Transformer Drawer.
Figure 9. Transformer Drawer in the Retracted Position.
F . Install the front cover and check the transformer fuse static
ground plunger devices:
1 . Install and bolt the front compartment cover in place . Lift
the cover in line with the compartment and align the slots on
the cover with the protruding brackets on the compartment
side sheets (see
Figures 6 and 7) . Push the cover into place
and allow the cover to drop down to its final bolting location .
Bolt the cover in place . The transformer drawer is fitted with
a safety plate that blocks access to the racking screw until
the drawer is in the compartment and the front compartment
cover is in place (see Figure 7) .
Fuse Tube
Nut
Secondary
Contacts
Contact
Plunger
Fully
Retracted
Position
Lower Half
Section of
Drawer
Upper Half
Section of
Drawer
G . Movement of the transformer drawer from the Disconnect posi-
tion to the Connect position:
1 . Rotate the racking cover plate knob to expose the nut at the
front of the racking screw on the transformer drawer (see
Figure 6) .
2 . Place the socket of the levering crank through the cover and
onto the racking screw nut . Rotate the levering crank clock-
wise until the transformer drawer is in the Connect position .
The Connect position is reached when the torque limiter on
the levering crank “breaks” free . Check to make sure the pri-
mary and the secondary contacts (see
when the transformer drawer is in the Connect position . Use
the “lighting out” or “ringing” methods to verify .
3 . Verify that the primary shutters are open and have operated
properly . The shutters can be viewed from within the closed
compartment through the viewing window on the front
cover .
4 . The front cover can not be removed when a transformer
drawer is in the Connect position . The transformer drawer
must be in the Disconnect position to remove the cover .
When the drawer is moved to the Connect position, a
mechanical linkage system on the compartment side sheet,
operated by a bracket on the transformer drawer, engages
a link with a bracket on the bottom left corner of the front
cover, preventing the cover from being removed (see Figures
H . Movement of the transformer drawer from the Connect position
to the Disconnect position:
1 . Rotate the racking cover plate knob to expose the nut at the
front of the racking screw on the transformer drawer (see
Figure 6) .
2 . Place the socket of the levering crank through the cover and
onto the racking screw nut . Rotate the levering crank coun-
ter-clockwise until the transformer drawer stops and is in the
Disconnect position .
3 . Verify that the primary shutters are closed and have operated
properly . The shutters can be viewed from within the closed
compartment through the viewing window on the front
cover .
4 . The front cover can now be unbolted and removed because
the drawer is in the Disconnect position .
I . Disengaging and removing the transformer drawer from the aux-
iliary compartment . Refer to the portable lift device instructions
in the optional accessories section of this document for proper
positioning of the lifting device prior to performing the following
actions:
1 . With the portable lifting device in position and the trans-
former drawer in the Disconnect position, grasp and firmly
pull the red drawer release handle on the front of the drawer
(see Figure 7) . This will unlatch the drawer from the compart-
ment .
2 . Pull the drawer onto the pan on the lifting device and latch
the drawer in place on the lifter .
3 . When removing the drawer from a lower compartment, it is
only necessary to unlatch the drawer, pull, and roll the drawer
directly onto the floor .
Step 12: Perform loading check on both the control and primary cir-
cuits to ensure the system is ready for operation .