Instruction Book
Page 2
Effective: May 2016
For more information visit:
www.Eaton.com
IB131017EN
Table 1.1 VCP-TL and VCP-TRL Ratings (ANSI C37.04 and C37.09)
Identification Rated Values
Circuit
Breaker
Type
Voltage
Class
Insulation Level
Continuous
Current
Shod Circuit
Breaking
Current
Shod Circuit
Making
Current
Mechanical
Endurance
Operations
Power
Frequency
Impulse
Withstand
kV rms
kV rms
kV Peak
Amperes
kA rms
kA Peak
VI
Mech.
50 VCP-TL16
and
50 VCP-TRL16
4.76
19
60
600
1200
1600
16
42
30000
100000
50 VCP-TL20
and
50 VCP-TRL20
4.76
19
60
600
1200
1600
20
52
30000
100000
50 VCP-TL25
and
50 VCP-TRL25
4.76
19
60
600
1200
1600
25
65
30000
100000
75 VCP-TL16
and
75 VCP-TRL16
8
.
25
20
60
600
1200
1600
16
42
30000
100000
75 VCP-TL20
and
75 VCP-TRL20
8.25
20
60
600
1200
1600
20
52
30000
100000
75 VCP-TL25
and
75 VCP-TRL25
8
.
25
20
60
600
1200
1600
25
65
30000
100000
150 VCP-TL16
and
150 VCP-TRL16
15
36
95
600
1200
1600
16
42
30000
100000
150 VCP-TL20
and
150 VCP-TRL20
15
36
95
600
1200
1600
20
52
30000
100000
150 VCP-TL25
and
150 VCP-TRL25
15
36
95
600
1200
1600
25
65
30000
100000
Use 15kV Breaker and Cassette when 95kV Impulse Withstand required
Also 2 Second Short Time Current Rating
Tested for capacitor switching capabilities. “General Purpose” to ANSI C37: Cable charging = 25A. "Definite Purpose" to ANSI C37: Back-to-back equals
250A and 1000A. Ratings of 250 and 1000A cover capacitor bank applications from 75 to 1000A. Inrush current and frequency rating = 18 kApk at 2.4 kHz."
1600A VCP-TL Drawout Breaker not available