background image

6

F. Sound Levels 10.

Although system noise levels can be reduced by modifying
pump design, fluid conditions also play a major part in
reducing system noise levels.

Some of the major factors affecting the fluid conditions that
cause the loudest noises in a hydraulic system are:

1.  Very high viscosities at start-up temperatures can

cause pump noise due to cavitation.

2.  Running with a moderately high viscosity fluid will

impede the release of entrained air. The fluid will not be
completely purged of such air in the time it remains in the
reservoir before recycling through the system.

3.  Aerated fluid can be caused by ingestion of air

through the pipe joints of inlet lines, high velocity discharge
lines, cylinder rod packings or by fluid discharging above the
fluid level in the reservoir. Air in the fluid causes a noise
similar to cavitation.

G. Overload Protection 11.

Relief valves limit pressure in the system to a prescribed
maximum and protect components from excessive pressure.
The setting of the relief valve depends on the work
requirements of the system.

H. Start-Up 12.

With a minimum drive speed of 600 RPM, a pump should
prime almost immediately if provision is made to initially
purge the air from the system.

Failure to prime within a reasonable time may result in
damage due to lack of lubrication. The pump inlet line must
be filled with fluid and must be tight and free from air leaks. It
may be necessary to crack a fitting on the outlet side of the
pump to purge air trapped in the system.

Section V – Service and Maintenance

A. Circuit Inspection 13.

Periodic inspection of the fluid condition and tube or pipe line
connections can save time-consuming breakdowns and
unnecessary parts replacement. The following should be
checked regularly:

1.  All hydraulic connections must be kept tight. A loose

connection in a pressure line will permit the fluid to leak out.
If the fluid level becomes so low as to uncover the inlet pipe
opening in the reservoir, extensive damage to the pump can
result. In suction or return lines, loose connections permit air
to be drawn into the system resulting in noisy and/or erratic
operation.

2.  Clean fluid is the best insurance for long service life.

Therefore, the reservoir should be checked periodically for
dirt or other contaminants. If the fluid becomes
contaminated, the system should be drained and the
reservoir cleaned before new fluid is added.

3.  Filter elements also should be checked and replaced

periodically. A clogged filter element results in a higher
pressure drop. This can force particles through the filter
which would ordinarily be trapped, or can cause the by-pass
to open, resulting in a partial or complete loss of filtration.

4.  Air bubbles in the reservoir can ruin the pump and

other components. If bubbles are seen, locate the source of
the air and seal the leak.

5.  A pump which is running excessively hot or noisy is a

potential failure. Should a pump become noisy or
overheated, the machine should be shut down immediately
and the cause of improper operation corrected.

B. Adding Fluid to the System 14.

When hydraulic fluid is added to replenish the system, it
should always be poured through a clean wire screen (200
mesh or finer) or preferably pumped through a 10 micron
(absolute) filter.

It is important that the fluid be clean and free of any
substance which could cause improper operation or wear of
the pump or other hydraulic units. Therefore, the use of cloth
to strain the fluid should be avoided to prevent lint getting
into the system.

C. Adjustments 15.

No periodic adjustments are required, other than to maintain
proper shaft alignment with the driving medium.

D. Lubrication 16.

Internal lubrication is provided by the fluid in the system.
Lubrication of the shaft coupling should be as specified by
their manufacturers. Coat shaft splines with a dry lubricant
(Molycoat or equivalent) to prevent wear.

E. Replacement Parts 17.

Reliable operation throughout the specified operating
range is assured only if genuine Vickers parts are used.
Sophisticated design processes and material are used
in the manufacture of our parts.

Substitutes may result in early failure. Part numbers are
shown in the parts drawings listed in Table 1.

Repair Kits – Commonly replace parts usually provided
in the form of a kit. (See Figure 4.) It is recommended
that all such parts be replaced with the kit when a unit is
overhauled.

Summary of Contents for Vickers 25V Series

Page 1: ...I 3157 S Reprinted 6 1 96 Quiet Intra Vane Single Pumps 25V T 35V T 45V T Series 20 Design 282 283 Series Service Data Vickers Vane Pumps ...

Page 2: ...ft Rotation 5 D Piping and Tubing 5 E Hydraulic Fluid Recommendations 5 F Sound Levels 6 G Overload Protection 6 H Start Up 6 V Service Maintenance A Circuit Inspection 6 B Adding Fluid to the System 6 C Adjustments 6 D Lubrication 6 E Replacement Parts 6 F Product Life 7 G Troubleshooting 7 VI Overhaul A Service Tools 8 B Unit Removal 8 C Disassembly 8 D Cleaning 9 E Inspection Repair and Replace...

Page 3: ...talog Installation 25V I 3158 S 25VT I 3154 S 35V I 3177 S 560 35VT I 3149 S 560 45V I 3159 S 45VT I 3151 S Table 1 Related Publications Model Code 2 2 4 5 6 7 8 9 10 11 1 Viton seals 1 3 12 3 Pump series Quiet intra vane type pump 4 Omit if not required Thru shaft connection mtg SAE 2 bolt adapter flange 5 SAE rated delivery USgpm 1200 RPM at 100 PSI A A flange B B flange C C flange 6 Port connec...

Page 4: ... rotor turns Centrifugal force and pressure under the vanes hold them out against the cam ring Pumping chambers are formed between the vanes and the cam ring and are enclosed by the two support plates The 282 283 series pumps are of a balanced intra vane design see Figure 2 Outlet pressure is constantly applied to the small intra vane area of the vane As the pump vane rotates through the high and ...

Page 5: ...s in tubing should be kept to a minimum to prevent excessive turbulence and friction of oil flow Tubing must not be bent too sharply The recommended minimum radius for bends is three times the inside diameter of the tube E Hydraulic Fluid Recommendations 9 General Data Fluid in a hydraulic system performs the dual function of lubrication and transmission of power It constitutes a vital factor in a...

Page 6: ...ystem resulting in noisy and or erratic operation 2 Clean fluid is the best insurance for long service life Therefore the reservoir should be checked periodically for dirt or other contaminants If the fluid becomes contaminated the system should be drained and the reservoir cleaned before new fluid is added 3 Filter elements also should be checked and replaced periodically A clogged filter element...

Page 7: ...and operate system until purged Bleed hydraulic lines at highest point down stream of pump while system is under pressure Vacuum condition Check inlet suction line and fittings for air leaks Oil too thick Be certain correct type of oil is used in system Warm up pump in cold weather until noise disappears Damaged or missing pump seals at mating surfaces Locate and replace damaged or missing seals C...

Page 8: ...f hydraulic oil source to pump inlet if an overhead reservoir is used 2 Remove the unit from the system 3 Cap all system and unit openings to prevent entry of dirt or moisture C Disassembly The index numbers on Figure 8 are in order of the disassembly sequence 1 Thoroughly clean pump exterior 2 Use a prick punch and mark the position of cover 4 with respect to the body 29 Mark position of the flan...

Page 9: ...eck bearing 25 for wear looseness and pitted or cracked races 3 Inspect the seal and bushing mating surfaces on shaft 26 for scoring and wear Replace the shaft if marks cannot be removed by light polishing F Assembly Refer to parts and service drawing listed in Table 1 for replacement parts Always replace old seals with new seals when overhauling a unit If a cartridge kit needs replacing new seals...

Page 10: ...ct adapter flange 6 to inlet cover 4 with four screws 5 NOTE Lockwashers are used with screw 5 for C adapter flanges only Torque screws 5 to specifications noted in Table 5 Screw 5 Torque Specifications Model Adapter Flange N m lb ft 25VT 35VT A or B 54 68 40 50 45VT 35VT C 31 40 23 30 45VT C 31 40 23 30 Table 5 Screw 5 Torque Specifications 11 Install key 2 on shaft 26 12 Place pump into mounting...

Page 11: ...ket Kit Key Screw Cover Screw Adapter Flange O Ring Spline Coupling Retaining Ring Screw Cartridge Kit items 12 22 Back up Ring O Ring Sealing Ring O Ring 1 1 4 1 4 1 A R 1 1 4 1 1 1 1 1 Item Nomenclature Qty 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Screw Inlet Support Plate Pin Ring Rotor Vanes Intra Vanes Outlet Support Plate Spirolox Ring Retaining Ring Bearing Shaft Washer Shaft Seal Body 2 1...

Reviews: