background image

5

The total pressure drop across the valves two series orifices
“A” and “B” must equal 1000 PSI, (the difference between
inlet and outlet pressures). The normal drop across orifice
“A” is between 60 and 80 PSI. (Use 75 PSI for this
explanation.) Orifice “B” will drop 925 PSI, the total of the
two pressure drops is the difference between inlet and outlet
pressures.

If the work load increases, the outlet pressure increases. To
keep a constant flow, the pressure drop across orifice “A”
must not change. This is accomplished as follows:

The increased outlet pressure is sensed against the spring
end of the hydrostat, causing it to move down, increasing the
area of orifice “B” and reducing the pressure drop across it.
This increases the pressure available at the up–stream side
of orifice “A”. 200 in

3

/minute will continue to flow as long as a

75 PSI pressure drop is maintained across orifice “A”.

If the work load were to decrease, (output PSI lower), a
similar set of events will begin, except in the opposite
direction. The hydrostat will move up. Orifice “B” reduces in
size, increasing the pressure drop across it, lowering the
pressure at the up–stream side of orifice “A” and a constant
200 in

3

/minute will continue to flow through the valve.

Torque Motor

 – A high force permanent magnet torque

motor imparts linear motion to the torque motor armature.
The deflection of the armature is directly proportional to
current through he torque motor coils. This armature is
linked to the metering spool with a wire and set screw. When
current is applied to the torque motor coils, the armature is
deflected to a certain position and the metering spool
follows, opening or closing orifice “A”. When orifice “A”
changes, the flow control will vary flow through the valve and
hold it constant at the new setting of the metering spool
regardless of workload.

Section IV – Installation and Operating Instructions

A. Installation Drawings

The installation drawing listed in Table 1 will show installation
dimensions and port locations.

B. Mounting

The FCGT- 02-*-11 Flow Control Valve is designed for man-
ifold or subplate mounting. Refer to the installation drawing
for subplate dimensions.

C. Piping And Tubing

1. All pipes and tubing must be thoroughly cleaned

before installation. Recommended methods of cleaning are
sand blasting, wire brushing and pickling.

NOTE

For instructions on pickling, refer to instruction
sheet 1221 – S.

2. To minimize flow resistance and the possibility of

leakage, only as many fittings and connections as are
necessary for proper installation should be used.

3. The number of bends in tubing should be kept to a

minimum to prevent excessive turbulence and friction of oil
flow. Tubing must not be bent too sharply. The
recommended radius for bends is three times the outside
diameter of the tube.

D. Hydraulic Fluid Recommendations

Oil in a hydraulic system performs the dual function of
lubrication and transmission of power. It constitutes a vital
factor in a hydraulic system, and careful selection should be
made with the assistance of a  reputable supplier. Proper
selection of oil assures satisfactory life and operation of system
components with particular emphasis on hydraulic valves.

Data sheet I-286-S for oil selection is available from Vickers
Technical Publications, Troy, MI 48007-0302.

Oil recommendations noted in the data sheet are based on our
experience in industry as a hydraulic component manufacturer.

Where special considerations indicate a need to depart from
the recommended oils or operating conditions, see your
Vickers representative.

Cleanliness

Thorough precautions should always be observed to insure
the hydraulic system is clean.

1. Clean (flush) entire new system to remove paint, met-

al chips, welding shot, etc.

2. Filter each change of oil to prevent introduction of

contaminants into the system.

3. Provide continuous oil filtration to remove sludge, and

products of wear and corrosion generated during the life of
the system.

4. Provide continuous protection of system from entry of

airborne contamination, by sealing the system and/or by
proper filtration of the air.

5. During usage, proper oil filling and servicing of filters,

breathers, reservoirs, etc., cannot be over emphasized.

6. Thorough precautions should be taken, by proper

system and reservoir design, to insure that aeration of the oil
will be kept to a minimum.

E. Overload Protection

A relief valve is required to limit pressure in the system and to
protect components from excessive pressure. The relief valve
should be connected in the circuit at the outlet of the pump,
before the FCGT flow control valve. The relief valve pressure
setting should be adjusted just above the minimum work
requirements of the system. DO NOT exceed the pressure
rating of any system component or a malfunction may result.

Summary of Contents for Vickers FCGT-02-A-004-11

Page 1: ...I 3419 S Reprinted 6 1 96 Remote Flow Control Valves FCGT 02 A B 11 S30 Overhaul Manual Vickers Flow Controls...

Page 2: ...Installation Drawing 5 B Mounting 5 C Piping and Tubing 5 D Hydraulic Fluid Recommendations 5 E Overload Protection 5 V Service and Maintenance 6 A Inspection 6 B Adding Fluid to the System 6 C Adjust...

Page 3: ...ariations within each basic model series are covered in the model code Table 2 is a complete breakdown of the model codes covering these units Service inquiries should always include the complete unit...

Page 4: ...ow Control Valve as being two distinct and separate systems one a standard compensated flow control with a fixed throttle setting and secondly an electrically modulated device torque motor used to var...

Page 5: ...g wire brushing and pickling NOTE For instructions on pickling refer to instruction sheet 1221 S 2 To minimize flow resistance and the possibility of leakage only as many fittings and connections as a...

Page 6: ...ed Sophisticated design processes and materials are used in the manufacture of our parts Substitutions may result in early failure Part numbers are shown in the parts listing reference Figure 3 F Prod...

Page 7: ...es 4 Symbolize each wire with a piece of tape to allow reassembly to the same pin of the connector Unsolder the four wires from connector 4 Remove connector and gasket 5 NOTE Hold the valve over a con...

Page 8: ...Ring O Ring Screw Elect Connector Gasket Screw Cover Screw Lockwasher Torque Mtr 280 Ohms Torque Mtr 2200 Ohms Torque Mtr 5300 Ohms Torque Mtr 40 Ohms Spacer Spool wire screw S A Spool wire screw S A...

Page 9: ...luded in the following steps See Figure 3 1 If nameplate 32 was removed install a new name plate with four screws 31 2 Install parts 29 through 24 into body 30 If seat 27 or check valve 26 were defect...

Page 10: ...resistance ohms wire code Series aiding Parallel Differential 40 Yellow 150 ma 300 ma N A 280 White 50 ma 100 ma 100 ma 2200 Blue 20 ma 40 ma 40 ma 5300 Black 12 5 ma 25 ma 25 ma Table 5 Input curren...

Page 11: ...il 3000 PSI is read on gage 5 and globe valve 1 is completely closed d Open globe valve 6 NOTE Valve may be unstable until all air is purged from the system Allow at least one minute for valve to stab...

Page 12: ...delivering 0 300 mA DC to a 20 OHM inductive load 10 Pressure gage 0 3000 psi 11 Load relief valve 12 Globe valve 13 Flow meter 14 Electric drive motor approximately 10 hp for 5 gpm 3000 psi 15 1 2 G...

Reviews: