4
15kV Class Padmount VisoVac™
instruction manual
MN024004EN April 2021
4.50
[114]
4.50
[114]
4.50
[114]
(18)
6.44
[164]
6.44
[164]
2.00
[51]
2.00
[51]
2.00
[51]
2.00
[51]
12.00
[305]
12.00
[305]
12.00
[305]
12.00
[305]
6.47
[164]
6.47
[164]
80.91
[2055]
18.00
[457]
18.00
[457]
18.00
[457]
18.00
[457]
81.00
[2057]
18.00
[457]
18.00
[457]
18.00
[457]
18.00
[457]
Ø.56
[Ø14]
Figure 7 . Double-sided base mounting (inches [mm])
Control voltages
The switchgear is available in most commonly used AC
and DC voltages for control power and comes pre-wired to
reduce on-site field installation time. Users should reference
the electrical wiring schematics for details on the specific
control and auxiliary voltages used in the equipment. Note
that in some cases two different voltages may be used, one
class for protection and another for heaters or other ancillary
equipment.
Control Voltages available:
AC Control Voltages
DC Control Voltages
110 VAC
24 VDC
120 VAC
48 VDC
220 VAC
110 VDC
240 VAC
125 VDC
220 VDC
250 VDC