12
InStALLAtIon And opErAtIon mAnuAL
25-13741-E
January 2020 www.eaton.com
9. Overview
technical specifications
Unless otherwise stated, following technical specifications apply to the
VoCALL 16 product range:
Feature
Range
Standards compliance
BS 5839 – 9:2011*
EMC
EN 55103-2:2009
EN 55032:2015 (Emission)
EN 55035:2017 (Immunity)
PSU
EN54-4
Cable (recommended)
1x4 or 2x2 core enhanced FP 200
Max. distance between two Outstations 200m
Max loop length - Outstations
2000m
Network configuration
Loop Wired – Outstation
AC supply voltage - Input
230V ± 10% RMS 50/60 Hz AC
Temperature (operating and storage)
-5°C up to +40°C
Humidity
98% Non-Condensing
IP Rating
IP20
*BS 5839-9: 2011 Fire detection and fire alarm systems for buildings. Code of
practice for the design, installation, commissioning and maintenance of emergency
voice communication systems.
ote:
n
Cabling to comply with local regulations and codes of practice.