87
InStALLAtIon And opErAtIon mAnuAL
25-13741-E
January 2020 www.eaton.com
14. Logging facility
14.3 Event log
VoCALL 16 facilitates the logging of important system events. The event log is
accessible using the display under “Event Log” option. Date and time stamp is
recorded for all events.
Event Type
Log Text
Description
Power Cycle
SOFTWARE RESET
Reset caused by software eg. After factory defaults.
POWER RECYCLE
Loss of power to the board.
LOW POWER RESET
Reset caused due to inadequate power supply
BROWN OUT RESET
Reset of system caused by Watchdog
Configuration
Parameters
TIME SET
Time is set on MASTER panel
DATE SET
Date is set on MASTER panel
SERVICE DATE SET
Service date is set on MASTER panel
SYSTEM SETTINGS SET
System settings updated from default values
DISPLAY SETTINGS SET
Display settings updated from default values
USER PIN CHANGED
Change in PIN of any USER
USER SETTING CHANGED
Change in settings of any USER
WEBSERVER SETTINGS SET
Change in default Webserver settings
Config Backup
/ Restore
RESTORE DISPLAY SETTINGS
Display settings restored to factory default values
RESTORE SYSTEM SETTINGS
System settings restored to factory default values
RESTORE PIN SETTINGS
User settings restored to factory default values
RESTORE WEBSERVER
SETTINGS
Webserver settings restored to factory default values
RESTORE WEBSERVER
USER SETTINGS
Webserver user settings restored to factory default values
PANEL CONFIG BACKUP
Configuration file backed up on SD card for panel
PANEL CONFIG RESTORE
Configuration settings restored from a file for panel
Event Log (1-230)
01/01/19 01:23.50
Sounder Silenced
1
02/03/19 10:54.30
Sounder Silenced
2
06/03/19 09:05.50
Accept Faults
3
Summary of Contents for VoCALL 16
Page 96: ...96 Installation and operation manual 25 13741 E January 2020 www eaton com 17 Log Viewer...
Page 103: ...103 Installation and operation manual 25 13741 E January 2020 www eaton com 18 Webserver...
Page 115: ...115 Installation and operation manual 25 13741 E January 2020 www eaton com Notes...