background image

VoCALL 5

Line Exchange Unit

Installation and Operation Manual

Summary of Contents for VoCALL 5

Page 1: ...VoCALL 5 Line Exchange Unit Installation and Operation Manual...

Page 2: ...anning the Wiring 10 5 2 Mains Connection 10 5 3 VoCALL 5 Wiring 11 5 4 Outstation Wiring 11 5 5 Cable Type 11 5 6 Outstation Wiring Type A 12 5 7 Outstation Wiring Type B 12 6 AUXILIARY CONNECTIONS 1...

Page 3: ...dicates a potentially hazardous situation which if not avoided can result in minor to moderate injury or serious damage to the product General Safety Precautions NOTICE The operating system of the con...

Page 4: ...nts Before handling any static sensitive items operators should get rid of any electrostatic charge by touching a sound safety earth such as a radiator Always handle PCBs by their sides and avoid touc...

Page 5: ...ractice such as BS9999 Disabled refuge systems are recommended in buildings where public or disabled staff gain access to any floor other than the ground floor using lifts 1 2 Product Overview A VoCAL...

Page 6: ...itted to line sockets Verify the following items are present 1 5x Outstation Line Connectors 2 1x 2 Way Fault Connector 3 1x 2 Way In Use Connector 4 1x 2 Way Access Connector If there are any items m...

Page 7: ...the Low Voltage Directive LVD accidentally knocked out holes should be blanked off 4 1 Surface Mount EFVCC5 When mounting the surface mount version to the wall ensure the unit sits flat on the wall a...

Page 8: ...ls For correct fitting of the flush mount cover the VoCALL 5 back box should be recessed into the wall so that the front of the unit is level with the finished surface of the wall The flush plate will...

Page 9: ...f the panels For correct fitting of the semi flush bezel the VoCALL 5 back box should be recessed into the wall so that the rear edges of the front plate line up with the finished surface of the wall...

Page 10: ...ystem specifications which demand a certain cable type providing it meets the appropriate national wiring regulations 5 1 Planning the Wiring All system wiring should be installed to meet the appropri...

Page 11: ...nts and emergency assist alarm the 3K9 resistor is simply removed from the terminal blocks when the outstation is connected for jack points the EOL resistor is moved to the OUT of the last jack on the...

Page 12: ...ary connections as shown below Figure 8 Auxiliary Connection Connections inside the Network VoCALL 5 Line Connector on Network VoCALL 5 to Type B line Line Connector on Network VoCALL 5 to Type B line...

Page 13: ...itted during standard applications 6 2 Powering Up Carefully check the outstation wiring then apply AC power to the VoCALL 5 unit DO NOT commission on batteries as the power supply has a large reservo...

Page 14: ...tallation and Operation Manual 25 13400 C May 2019 www eaton com 7 Batteries 7 1 Battery fitting Figure 9 Inserting the batteries not included 7 2 Battery wiring Figure 10 Wiring the batteries not inc...

Page 15: ...removing the mains power always remove the negative Black terminal first 8 Operation All conversations on the VoCALL 5 system are under the command of the control handset 8 1 Receiving a call at the...

Page 16: ...ound and all status LEDs will Light 8 5 Indications and Controls Figure 11 Indication and Controls Indicators Green Mains Indicates healthy mains Battery Indicates healthy battery and charger healthy...

Page 17: ...responsible person or their agent lift a different handset on the system each week and make a call to the control repeat each week until all points are tested record results in the site log 6 Monthly...

Page 18: ...rge Max Charge Current 1A Inputs Number of Lines 5 Remote Enable Short to use End of Line 3K9 Outputs Number 2 Fault In Use Type Volt free relay Contact 30V DC 1A Controls Buttons 6 five lines 1 fault...

Page 19: ...19 Installation and Operation Manual 25 13400 C May 2019 www eaton com Notes...