11
InstALLAtIon And opErAtIon MAnUAL
25-13400-C May 2019 www.eaton.com
5. Connecting VoCALL 5
5.3 VoCALL 5 Wiring
Figure 5. VoCALL 5 Wiring
5.4 Outstation Wiring
The VoCALL 5 system requires no programming to determine the
outstation configuration.
4 types of outstation are allowed on the system, type A (fixed phone) type B
(hands-free refuge points), jack plates and emergency assist alarm.
For type A telephones, type B refuge points and emergency assist alarm the
3K9 resistor is simply removed from the terminal blocks when the outstation is
connected, for jack points the EOL resistor is moved to the OUT of the last jack on
the system.
5.5 Cable Type
All cables on the VoCALL 5 system should be of a type required to comply with local
regulations. The unit will work with MICC to 200m per line and enhanced Soft Skin
cables to 500m per line.
P1
MASTER HANDSET
TO MASTER
HANDSET
OUTSTATION
CONNECTIONS
VOLT-FREE
OUTPUTS
P2
OUTST
ATION 1
OUTST
ATION 2
OUTST
ATION 3
OUTST
ATION 4
OUTST
ATION 5
FAUL
T
IN-USE
ENABLE
FL
T13
FL
T14
P3
P4
3K9
3K9
3K9
P5
P6
P8
P7
P10