background image

Chapter 2.1.1. – 3

EATON CORPORATION

xxxxx+xxxx-xxxxEN

Residual Current Devices

Hints for the application of our frequency converter-proof RCDs:

Frequency converters are used in a wide variety of systems and equip-
ment requiring variable speed, such as lifts, escalators, conveyor
belts, and large washing machines. Using them for such purposes in
circuits with conventional residual current devices causes frequent
problems with unwanted tripping.

The technical root cause of this phenomenon is the following: Fast
switching operations involving high voltages cause high interference
levels which propagate through the lines on the one hand, and in the
form of interfering radiation on the other. In order to eliminate this
problem, a mains-side filter (also referred to as input filter or EMC-fil-
ter) is connected between the RCD and frequency converter. The anti-
interference capacitors in the filters produce discharge currents
against earth which may cause unwanted tripping of the RCD due to
the apparent residual currents. Connecting a filter on the output side
between frequency converter and 3-phase AC motor results in the
same behaviour.

Due to the currents flowing off through the filters (designated IF), the sum of
currents through the RCD is not exactly zero, which causes unwanted tripping.

This sample tripping characteristic of a 100 mA RCD and a 300 mA
RCD shows the following: In the frequency range around 50 Hz, the
RCDs trip as required (50 - 100 % of the indicated I

Δ

n

).

In the range shown hatched in the diagram, i. e. from approx. 100 to
300 Hz, unwanted tripping occurs frequently due to the use of fre-
quency converters. Frequency converter-proof residual current
devices are much less sensitive in this frequency range than in the 50
- 60 Hz range, which leads to an enormous increase in the reliability of
systems.

Therefore, we recommend to use frequency converter-proof RCDs!

These special residual current devices can be recognised by an extension
of the type designation ("

-U

"). They meet the requirements of compatibil-

ity between RCDs and frequency converters with respect to unwanted
tripping.

These are 

NOT AC/DC-sensitive

RCDs of type B !!!

Our 

RCDs of type "-U"

are characterised by 

SENSITIVITY TO  RESIDUAL

PULSATING DC

and 

SELECTIVITY

or 

SHORT-TIME DELAY

.

G

S

Tripping characteristic

Protective Measures

In Austria, the ÖVE Decision EN 219 is applicable. 

Under this standard

• frequency converters must be equipped with current limiting

devices in order to ensure disconnection in cause of faults or over-
load, and

• the installer of a system is obliged to make sure that additional

equipotential bonding is provided (additional inclusion of all metal
components, such as frequency converters, mains filters, motor fil-
ters, etc. into the existing equipotential bonding), in order to ensure
that the permissible touch voltage of 50 V AC or 120 V DC is not
exceeded. (In ÖVE/ÖNORM E 8001-1 the term "touch voltage" has
been omitted. There is only a fault voltage limit of 65 V AC or 120 V
DC which must not be exceeded).

In Germany, VDE 0100 is applicable, in Switzerland SEV 1000.

In case of application in any 

other country

than those mentioned

take into account national rules and recommendations.

The following rules for the application of RCDs of type" -U" are only applicable in those cases where an RCD of type "-B" is not explicitly demanded in the
instructions of the manufacturer of the frequency converter.

How can you make sure that the required protective measures are in place when using RCDs type “-U” and frequency converters in one system?

Mains

RCD

RCD

Mains-side filter

Mains-side filter

F

requency 

con

ver

ter

F

requency 

con

ver

ter

S

c

reened motor line

Mains side filter

Motor

Motor

Frequency converter
interference range
(approx. 100 - 300 Hz)

Summary of Contents for xEffect

Page 1: ...G min 10 ms time delay surge current proof up to 3 kA For system components where protection against unwanted tripping is compulsory to avoid personal injury and damage to property 12 1 6 of VE NORM E...

Page 2: ...ntional testing equipment which must be set according to the instructions for operation of the testing device Due to reasons inherent in the measuring process the tripping time determined in this way...

Page 3: ...s to an enormous increase in the reliability of systems Therefore we recommend to use frequency converter proof RCDs These special residual current devices can be recognised by an extension of the typ...

Page 4: ...e of leakage currents Integrated auxiliary contact Local Indication New level of accuracy reduced unwanted tripping No monthly test required Comprehensive range of accessories Real contact position in...

Page 5: ...ay application type R 4 pole 63 0 03 FRCdM 63 4 003 R 168636 1 30 SG49712 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM type S A Selective surge current proof t...

Page 6: ...pole device can also be used for 2 pole connection See connection possibilities The test key T must be pressed every year The system operator must be informed of this obligation and his responsibilit...

Page 7: ...ive surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80 A gG gL In 100A 100 A gG gL Endurance electric...

Page 8: ...shing yellow red Check the device with test key If the LEDs are still flashing check the direction of connection supply side load side Remote Indication Potential free auxiliary switch for use in cont...

Page 9: ...ndication through 3 LEDs B types also meet the requirements of superior fire protection systems according to VDE 0664 400 formerly known as VDE V 0664 110 4 pole types can also be used as 2 pole devic...

Page 10: ...7900 1 30 40 0 3 FRCdM 40 4 03 S B 167901 1 30 63 0 3 FRCdM 63 4 03 S B 167902 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ G B Surge current...

Page 11: ...1 30 40 0 3 FRCdM 40 4 03 G Bfq 167905 1 30 63 0 3 FRCdM 63 4 03 G Bfq 167906 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ S Bfq Selective su...

Page 12: ...residen tial and similar applications Under all other conditions e g damp ly or dusty environment it s recommended to test in shorter inter vals e g monthly A test is further needed if red and yellow...

Page 13: ...Type S B S B and S Bfq typ 5 kA 8 20 s selective surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80...

Page 14: ...of connection supply side load side Remote Indication Potential free auxiliary switch for use in control circuits insulated from main circuit of the switch gear according to IEC EN60664 0 25A ohmic l...

Reviews: