background image

Chapter 2.2.1. – 4

EATON CORPORATION

xxxxx+xxxx-xxxxEN

Residual Current Devices

Connection diagram

4-pole

Technical Data

FRCdM

Electrical

Design according to 

IEC/EN 61008

Type G and G/A acc. to ÖVE E 8601

Current test marks as printed onto the device

Tripping

instantaneous

Type G , R 

10 ms delay

Type S 

40 ms delay - with selective disconnecting function

Type U (only 30 mA) 

10 ms delay

Type U (except 30 mA) 

40 ms delay - with selective disconnecting function

Rated voltage

U

n

240/415 V AC,  50Hz

Operation voltage electronic

50 – 264V AC

Operation voltage test circuit

196 – 264V AC

Rated tripping current

I

Δ

n

30, 300 mA

Sensitivity

AC and pulsating DC

Rated insulation voltage

U

i

440 V

Rated impulse withstand voltage

U

imp

4 kV (1.2/50µs)

Rated short circuit capacity

I

cn

10 kA

Peak withstand current

Type G, G/A, R, U (30mA) 

3 kA (8/20 µs) surge current proof

Type S/A, U (except 30mA) 

typ. 5 kA (8/20 µs) sel surge current proof

Electrical isolation 

> 4 mm contact space

Maximum back-up fuse 

Short circuit and overload protection

I

n

= 16-63A 

63 A gG/gL

I

n

= 80A 

80 A gG/gL

I

n

= 100A 

100 A gG/gL

Endurance

electrical components

4,000 operating cycles

mechanical components 

20,000 operating cycles

Mechanical

Frame size 

45 mm

Device height 

80 mm

Device width 

70 mm (4MU)

Mounting 

quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715

Degree of protection, built-in 

IP40

Degree of protection in moisture-proof enclosure

IP54

Upper and lower terminals 

open mouthed/lift terminals

Terminal protection 

finger and hand touch safe, BGV A3, ÖVE-EN 6

Terminal capacity 

1.5 - 35 mm

2

single wire

2 x 16 mm

2

multi wire

Terminal screw 

M5 (Pozidriv PZ2)

Terminal capacity warning contact(s) 

0.25-1.5 mm

2

(plug in terminals)

Terminal torque 

2 - 2.4 Nm

Busbar thickness 

0.8 - 2 mm

Tripping temperature 

-25°C to +40°C

Storage- and transport temperature 

-35°C to +60°C

Resistance to climatic conditions 

25-55°C/90-95% relative humidity acc. to IEC 60068-2

Contact position indicator 

red / green

Tripping indicator 

white / blue

Summary of Contents for xEffect

Page 1: ...G min 10 ms time delay surge current proof up to 3 kA For system components where protection against unwanted tripping is compulsory to avoid personal injury and damage to property 12 1 6 of VE NORM E...

Page 2: ...ntional testing equipment which must be set according to the instructions for operation of the testing device Due to reasons inherent in the measuring process the tripping time determined in this way...

Page 3: ...s to an enormous increase in the reliability of systems Therefore we recommend to use frequency converter proof RCDs These special residual current devices can be recognised by an extension of the typ...

Page 4: ...e of leakage currents Integrated auxiliary contact Local Indication New level of accuracy reduced unwanted tripping No monthly test required Comprehensive range of accessories Real contact position in...

Page 5: ...ay application type R 4 pole 63 0 03 FRCdM 63 4 003 R 168636 1 30 SG49712 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM type S A Selective surge current proof t...

Page 6: ...pole device can also be used for 2 pole connection See connection possibilities The test key T must be pressed every year The system operator must be informed of this obligation and his responsibilit...

Page 7: ...ive surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80 A gG gL In 100A 100 A gG gL Endurance electric...

Page 8: ...shing yellow red Check the device with test key If the LEDs are still flashing check the direction of connection supply side load side Remote Indication Potential free auxiliary switch for use in cont...

Page 9: ...ndication through 3 LEDs B types also meet the requirements of superior fire protection systems according to VDE 0664 400 formerly known as VDE V 0664 110 4 pole types can also be used as 2 pole devic...

Page 10: ...7900 1 30 40 0 3 FRCdM 40 4 03 S B 167901 1 30 63 0 3 FRCdM 63 4 03 S B 167902 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ G B Surge current...

Page 11: ...1 30 40 0 3 FRCdM 40 4 03 G Bfq 167905 1 30 63 0 3 FRCdM 63 4 03 G Bfq 167906 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ S Bfq Selective su...

Page 12: ...residen tial and similar applications Under all other conditions e g damp ly or dusty environment it s recommended to test in shorter inter vals e g monthly A test is further needed if red and yellow...

Page 13: ...Type S B S B and S Bfq typ 5 kA 8 20 s selective surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80...

Page 14: ...of connection supply side load side Remote Indication Potential free auxiliary switch for use in control circuits insulated from main circuit of the switch gear according to IEC EN60664 0 25A ohmic l...