4 XN-312-GW-EC gateway object dictionary
4.3 Device parameter area
34
XN-312-GW-EC gateway
07/20 MN050010-EN Eaton.com
4.3 Device parameter area
The device parameter area contains all the parameters that belong to the
EtherCAT device (gateway). Object information is shown in XSOFT-CODE-
SYS-3 in online mode.
Sub-index
(hex)
Descrip-
tion
Default
Catalog
number
Access
#00
number of
entries
–
USINT
ro
#01
module
status
-
(0 = Module OK)
UDINT
ro
#02
device ID
00000000
hex
UDINT
ro
#03
FPGA
version
00000000
hex
UDINT
ro
#04
HW version
00000000
hex
UDINT
ro
#05
Serial
number
0
Visible string
ro
#06
Firmware
version
00000000
hex
UDINT
ro
Index
Sub-index
Description / Value
0xF000
Modular device profile
The modular device profile object contains all information required in order to
interpret the object area's module objects.
Sub-index #01
Module index distance (16)
Maximum number of objects per module.
Sub-index #02
Maximum number of modules (32)
Max. 32 modules on the gateway
Sub-index #03
General configuration
Available sub-indices in the 0×8xx0 general configuration objects
Sub-index #04
General information
Available sub-indices in the 0×9xx0 general information objects
Sub-index #05
Module PDO group of devices
0xF030
Configured module ident list,
ID list of the configured XN-322 modules
0×F030: Sub-
index#01...#20
SubIndex 001 -SubIndex 020
Module ID number as per the module's position in the XN300 configuration (1
to 32)
0xF050
Detected module ident list,
ID list of mounted XN-322 modules
0×F050: Sub-
index#01...#20
SubIndex 001 -SubIndex 020
Module ID number as per the module's position in the XN300 system (1 to 32)
0xF100
System bus version
Sub-index #01
Systembus manager protocol version