5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
141
105
(69h)
Module order
name
G
SHORT
STRING
Contains the name of the module, for
example, "XN-4AI-U/I".
106
(6Ah)
Module revision
G
USINT
Contains the revision number of the module
firmware.
107
(6Bh)
Module type ID
G
ENUM
USINT
Describes the module type: see attribute
107 (6Bh) on page 86
108
(6Ch)
Module
command inter-
face
G/S
ARRAY
The control interface of the XI/ON module.
ARRAY OF:
BYTE: Control byte sequence
109
(6Dh)
Module response
interface
G
ARRAY
Response interface of the XI/ON module.
ARRAY OF:
BYTE: Response byte sequence
110
(6Eh)
Module regis-
tered
index
G
ENUM
USINT
Contains the index numbers specified in all
the module lists.
111
(6Fh)
Module input
channel count
G
USINT
Contains the number of input channels
supported by the module.
112
(70h)
Module output
channel count
G
USINT
Contains the number of output channels
supported by the module.
Input data
113
(71h)
to
128
(80h)
Module input 1
to
Module input 16
G
UINT
Input data of the module (according to chan-
nels).
Output data
129
(81h)
to
144
(8Fh)
Module output_1
to
Module
output_16
G
DWORD
Output data of the module (according to
channels).
Diagnosis data
145
(90h)
Range error
G
WORD
Indicates an over- or undercurrent of 1 % of
the set current/voltage range; whereby,
undercurrents can only be recognized with
those modules that have a set current range
of 4 to 20 mA.
146
(91h)
Open circuit error G
WORD
Indicates an open circuit in the signal line for
the operating mode
Table 60:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description