5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
142
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
147
(92h)
Short circuit error G
WORD
148
(93h)
reserved
-
-
-
Parameter data
149
(94h)
to
164
(A4h)
Channel 1
to
Channel 16
G/S
UINT
Activates or deactivates the corresponding
channel.
165
(A5h)
to
180
(B4h)
Operating mode
channel 1
to
Operating mode
channel 16
G/S
ENUM
Sets the operating mode for the channel
0 = deactivate channel
1 = -10 V…+10 V
2 = 0 V…+10 V
3 = 0 mA…20 mA
4 = 4 mA…2 0mA
181
(B5h)
to
196
(C4h)
Value representa-
tion channel 1
to
Value representa-
tion channel 16
G/S
ENUM
Sets the value representation for the chan-
nels:
0 = default
1 = 16 bit integer
2 = 12 bit left jus diagnostics.
Table 60:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description