4 Technical features
4.3 Technical data
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
33
Shock resistant according to
IEC/EN 60068-2-27
18 shocks, sinusoidal half-wave 15 g peak
value/11 ms, in each case in ± direction per
space coordinate
Resistance to repetitive shock according to
IEC/EN 60068-2-29
1 000 shocks, half-sinus 25 g peak value/6 ms,
in each case in ± direction per space coordinate
Topple and fall according to IEC/EN 60068-2-31 and free fall according to IEC/EN 60068-2-32
Height of fall (weight < 10 kg)
1.0 m
Height of fall (weight 10 to 40 kg)
0.5 m
Test runs
7
Device with packaging, electrically tested printed-circuit board.
A
The use in
residential areas
may lead to
functional errors.
Additional
suppression mea-
sures are neces-
sary!
Electromagnetic compatibility (EMC) according to IEC/EN 61000-6-2 (Industry)
Static electricity according to IEC/EN 61000-4-2
Discharge through air (direct)
8 kV
Relay discharge (indirect)
4 kV
Electromagnetic HF fields according to
IEC/EN 61000-4-3
10 V/m
Conducted interferences induced by HF
fields according to IEC/EN 61000-4-6
10 V
Fast transients (Burst) according to
IEC/EN 61000-4-4
1 kV / 2 kV
Emitted interference according to IEC/EN 61000-6-4 (Industry)
Emitted interference according to
IEC/CISPR 11 / EN 55011
Class A
A
Warning
This device can cause radio disturbances in residential areas and in small industrial
areas (residential, business and trading). In this case, the operator can be required
to take appropriate measures to suppress the disturbance at his own cost.
Note
For testing high energie surge (according to IEC/EN 61000-4-5 and product standard
IEC/EN 61131-2) a cable lenght of digital and analogue I/O ports is specified with
< 30 m.