5 Power distribution 0 V XN-322-18PD-M
5.3 Technical data
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
35
Figure 19:
XN-322-18PD-M and XN-322-18PD-P wiring example showing how to power
slice modules
5.3 Technical data
5.3.1 0 V distribution
PE
X1 1
X2
X3
X4
2
3
4
5
6
7
8
9 10 11 12
13 14 15 16 X5 17 18
24 V
0 V
24 24
XN300
24V 0V
XN300
24V 0V
X1 1
X2
X3
X4
2
3
4
5
6
7
8
9 10 11 12
13 14 15 16 X5 17 18
0V 0V
U
e24
XN322-PD-M
XN322-PD-P
Number of 0 V potentials
2
Short-circuit proof
no
Internal fusing
no
Maximum permissible contin-
uous load current / connection
8A
Maximum total current
16 A
(The maximum current of 8 A per connection must not be exceeded at the
inputs or outputs!)