8 Guidelines for Electrical Installation
8.3 Electromagnetic Compatibility (EMC)
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
153
8.3.5
Mounting rails
All mounting rails must be mounted onto the mounting plate with a low impedance, over a
large surface area, and must be correctly earthed.
Mount the mounting rails over a large surface area and with a low impedance to the support
system using screws or rivets.
Remove the isolating layer from all painted, anodized or isolated metal components at the
connection point. Protect the connection point against corrosion (for example with grease;
caution: use only suitable grease).
Figure 74:
Mounting
options
A
TS 35
B
Mounting rail
C
Mounting
plate