9 Appendix
9.1 Data image of the technology modules
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
161
ERR_LOAD
1: Error with load function
The control bits LOAD_UPLIMIT and LOAD_LOLIMIT must not be
set simultaneously during the transfer.
The value of LOAD_UPLIMT and LOAD_LOLIMIT was selected
outside of the permissible range.
Permissible values for LOAD_LOLIMIT:
0 to 199 999 999 x10
-3
Hz
0 to 24 999 999 x 10
-3
rpm
0 to 99 999 999 ms
Permissible values for LOAD_UPLIMIT:
1 to 200 000 000 x 10
-3
Hz
1 to 25 000 000 x 10
-3
rpm
1 to 100 000 000 ms
STS_LOAD
Status of load function
Set if the Load function is running.
STS_DN
Direction status: down.
The direction is determined by a signal at the physical input B. The
Signal evaluation parameter (A, B): must be set to pulse and direc-
tion.
STS_UP
Direction status: up.
The direction is determined by a signal at the physical input B. The
Signal evaluation parameter (A, B): must be set to pulse and direc-
tion.
STS_DO1
The DO1 status bit indicates the status of digital output DO1.
STS_DI
The DI status bit indicates the status of digital input DI.
STS_GATE
1: Measuring operation running.
STS_UFLW
1: The lower measuring limit was undershot.
The bit must be reset with RES_STS: 0
→
1.
STS_OFLW
1: The upper measuring limit was exceeded.
The bit must be reset with RES_STS: 0
→
1.
STS_CMP1
1: Measuring terminated^
The measured value is updated with every elapsed time interval.
The end of a measurement (expiry of the time interval) is indicated
with the status bit STS_CMP1.
The bit must be reset with RES_STS: 0
→
1.
Table 77:
Process input
data - measure-
ment mode of
XN-1CNT-
24VDC
Bits
Value, meaning