9 Appendix
9.1 Data image of the technology modules
190
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
Table 86:
Process input
data of
XNE-1SWIRE
Desig-
nation
Value
Meaning
SIx
Switch status, relay x
SIx supplies the switch status of the contactor coil of the SWIRE slave as
a feedback signal. SIx makes it possible to check whether the set switch
status was executed by a mechanical connection. This must take into
account the time delay between the setting of an output, a mechanical
execution and the subsequent feedback signal.
0
Off
Contactor coil is switched off
1
On
Contactor coil is switched on
PKZSTx
Switch status, PKZ x
0
Off
The motor-protective circuit-breaker is off or has tripped
1
On
The motor-protective circuit-breaker is switched on
SCx
Communication error, slave x
Setting the SC
DIAG
Sx parameter sets the SCx bit in the process input data.
The information is provided as status information in the PLC for the user.
0
ON LINE
Status of slave x: Everything o.k.
1
OFF LINE
Status of slave x: Slave diagnostics message present