5 Implementation of Modbus TCP
5.9 Parameters of the modules
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
69
5.9
Parameters of the modules
5.9.1
Analog input modules
• XN-1AI-I(0/4...20MA)
• XN-2AI-I(0/4...20MA)
(1 byte parameter per channel)
• XN-1AI-U(-10/0...+10VDC)
Table 17:
Module
parameters
A
Default-
settings
Byte Bit
Parameter
name
Value
0
0
Current mode
0 = 0..20mA
A
1 = 4..20mA
1
Value representation
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnostics
0 = release
A
1 = block
Table 18:
Module
parameters
A
Default-
settings
Byte Bit
Parameter
name
Value
0/1
0
Current mode
0 = 0..20mA
A
1 = 4..20mA
1
Value representation
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnostics
0 = release
A
1 = block
3
Channel Kx
0 = activate
A
1 = deactivate
Table 19:
Module
parameters
A
Default-
settings
Byte Bit
Parameter
name
Value
0
0
Voltage mode
0 = 0..10V
A
1 = -10..+10V
1
Value representation
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnostics
0 = release
A
1 = block