5 Implementation of Modbus TCP
5.9 Parameters of the modules
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
71
• XN-2AI-THERMO-PI (2 byte parameter per channel)
• XN-4AI-U/I (1 byte parameter per channel)
Table 22:
Module
parameters
A
Default-
settings
Byte Bit
Parameter
name
Value
0/1
0
Mains suppression Kx
0 = 50Hz
A
0 = 60Hz
1
Value representation Kx
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnostics Kx
0 = release
A
1 = block
3
Channel Kx
0 = activate
A
1 = deactivate
7 to 4
Element Kx
0000 = type K, -270..1370°C
A
0001 = type B, +100..1820°C
0010 = type E, -270..1000°C
0011 = type J, -210..1200°C
0100 = type N, -270..1300°C
0101 = type R, -50..1760°C
0110 = type S, -50..1540°C
0111 = type T, -270..400°C
1000 = +/-50 mV
1001 = +/-100 mV
1010 = +/-500 mV
1011 = +/-1000 mV
... = reserved
Table 23:
Module
parameters
A
Default-
settings
Byte Bit
Parameter
name
Value
0 to 3
0
Range
0 = 0..10V/ 0..20mA
A
1 = -10..+10V/ 4..20mA
1
Value representation
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnostics
0 = release
A
1 = block
3
Channel Kx
0 = activate
A
1 = deactivate
4
Operation mode
0 = voltage
A
1 = current