5 Implementation of Modbus TCP
5.9 Parameters of the modules
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
91
• XNE-1SWIRE
The following table shows the meaning of the parameter bits:
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 1
reserved
free
free
MC
MNA
Configura-
tion
Disable Cfg
free
Byte 2
free
U
AUXERR
TYP
ERR
TYP
INFO
PKZ
ERR
PKZ
INFO
SD
ERR
SD
INFO
Byte 3
reserved
Byte 4
reserved (lifeguarding time up to version VN 01-03)
Byte 5
SC
DIAG
S8
SC
DIAG
S7
SC
DIAG
S6
SC
DIAG
S5
SC
DIAG
S4
SC
DIAG
S3
SC
DIAG
S2
SC
DIAG
S1
Byte 6
SC
DIAG
S16
SC
DIAG
S15
SC
DIAG
S14
SC
DIAG
S13
SC
DIAG
S12
SC
DIAG
S11
SC
DIAG
S10
SC
DIAG
S9
Byte 7
reserved
Byte 8
reserved
Byte 9
- 24
Type designation slave 1 - 16
Table 35:
Module
parameters
Para-
meter
name
Value
A
Default-
settings
Byte 1
Disable Cfg Automatic SWIRE configuration
If the physical structure of the SWIRE bus does not match the configuration
stored in the XNE-1SWIRE on power up (SW LED flashing), the physical struc-
ture of the SWIRE bus must be stored in the XNE-1SWIRE.
0 = inactive
A
Manual SWIRE configuration:
To store the physical structure of the SWIRE bus in the XNE-
1SWIRE, the CFG button of the XNE-1SWIRE must be pressed
manually (only functions if the SW LED is flashing).
1 = active
Automatic SWIRE configuration:
If the physical structure of the SWIRE bus does not match the
configuration stored in the XNE-1SWIRE on power up, the
physical structure is stored automatically in the XNE-1SWIRE.
Configura-
tion
PLC configuration check
If the PLC configuration check is activated, the configuration stored in the XNE-
1SWIRE is compared with the SET configuration stored in the PLC.
0 = active
A
The configuration stored in XNE-1SWIRE is compared with the
SET configuration stored in the PLC. Only SWIRE slaves in the
SWIRE bus are accepted that have a device ID completely
matching the SET configuration.
1 = inactive
All slaves are mapped in 4Bit INPUT / 4Bit OUTPUT without
checking the device ID.