ROUTINE MAINTENANCE

 

 
 

WARNING:  

ENSURE THAT THE POWER CORD TO THE MACHINE 

 HAS BEEN  DISCONNECTED BEFORE CARRYING OUT 
  ROUTINE MAINTENANCE ON ITEMS 1, 2, 4, 5, AND 6. 

 

 

 
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be 
performed as follows: 
 

 

 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing the dirt out from 
behind the fins with compressed air.  Hold the nozzle of the air hose away from the 
coil (approx 6”) to avoid damaging the fins.  Alternatively, vacuum clean the coils. 

 
 
 

WARNING:  

DO NOT STEAM CLEAN REFRIGERATION COILS. 

 

 

 

 
 

2. 

Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.  

The fan motor is sealed for life and therefore does not need oiling.

 

 

 

3. 

To check the refrigerant charge, run the unit for 15 minutes and briefly remove the 
cover.  The evaporator coil should be evenly frost coated across its surface.  At 
temperatures above 25

°

C, the coil may be covered with droplets of water rather than 

frost.  Partial frosting accompanied by frosting of the thin capillary tubes, indicates 
loss of refrigerant gas or low charge.  

 
 

4. 

Check all wiring connections. 

 

 

5.  To check the operation of the defrost system, switch the machine on and leave it 

running for approximately 45 minutes.  The machine will then enter “Hot Gas” 
defrost mode for approximately 4 minutes before returning to normal operation.  If 
the unit will not defrost, the printed circuit timer board may be defective or the by-
pass valve may be inoperable. 

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO 

CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE

Summary of Contents for CD425

Page 1: ...2 Issue 1 Date 13 10 03 EBAC MODEL CD425 1018110 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News VA 23606 2575 Tel 757 873 6800 Fax 7...

Page 2: ...drain tray for collecting and disposing of condensed moisture f A cabinet to house the above components The fan draws the moist air through the evaporator coils which cools the air below its dew poin...

Page 3: ...1 Date 13 10 03 SPECIFICATIONS MODEL CD425 HEIGHT 1190 mm WIDTH 1100 mm DEPTH 460 mm WEIGHT 160 kg AIRFLOW 1750 CFM 3000M Hr TOTAL POWER 6 0Kw MAX MAXIMUM OPERATING TEMPERATURE 35 C 95 F POWER SUPPLY...

Page 4: ...Remove the front cover b Check the actual relative humidity inside the area c Set humidity control to a LOWER value than the actual relative humidity d After approximately 6 minutes check the compres...

Page 5: ...ng and flooding of the chamber WIRING Connect a suitably fused 3 phase mains power supply to the MAINS T B terminal block inside the electrical box located at the control panel end of the machine DRAI...

Page 6: ...for life and therefore does not need oiling 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the cover The evaporator coil should be evenly frost coated across its surf...

Page 7: ...of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak cau...

Page 8: ...breaker Little or no water extraction 1 Insufficient air movement 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 C...

Page 9: ...5kg Drain Tube 2014315 3 meters 3 8 Copper Tube 3014203 2 meters 1 2 Copper Tube 3014204 2 meters 5 8 Copper Tube 3014205 2 meters Cork Tape 3100223 1 2 Roll Fan Motor 3030140 1 Axial Fan 3010119 1 So...