TROUBLESHOOTING 

 
 
 

S

YMPTOM

 

C

AUSE

 

R

EMEDY

 

 

Unit inoperative  

1.  No power to unit 

1.  Check the power from the power  
      supply panel 

Little or no airflow 

1.  Loose fan on shaft 
2.  Fan motor burnt out 
3.  Dirty refrigeration coils 
4.  Loose electrical wiring 
5.  Fuse blown or circuit breaker  
     tripped 

1. Tighten fan 
2.  Replace the fan motor 
3. See 

Routine Maintenance

  Section 

4.  Check the wiring diagram to find 
  fault and repair 
5.  Replace the fuse or reset the 
 circuit 

breaker 

Little or no water extraction 

1.  Insufficient air movement 
2. Compressor fault 
3.  Loss of refrigerant gas 
4.  Blocked filter dryer 

1.  Check all of the above 
2.  Contact the Factory Service Center 
3.  Contact the Factory Service Center 
4.  Contact the Factory Service Center 

Unit vibrates excessively 

1.  Loose compressor 
2.  Damaged fan 

1.  Tighten the nuts on the compressor  
     mounts 
2.  Replace fan 

Water flooding inside the 
machine 

1.

 

Drain pipe blocked/frozen 

2.  Drain pipe too high 

1.  Clear the obstruction, straighten or  
      replace 
2.  No section of the drainage pipe 

 
 
 
 
 
 

 
 
 
 
 
 

Ebac Industrial Products, Inc. 

700 Thimble Shoals Blvd, Suite 109 

Newport News, VA. 23606-2575 

 
 

Summary of Contents for CD425

Page 1: ...2 Issue 1 Date 13 10 03 EBAC MODEL CD425 1018110 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News VA 23606 2575 Tel 757 873 6800 Fax 7...

Page 2: ...drain tray for collecting and disposing of condensed moisture f A cabinet to house the above components The fan draws the moist air through the evaporator coils which cools the air below its dew poin...

Page 3: ...1 Date 13 10 03 SPECIFICATIONS MODEL CD425 HEIGHT 1190 mm WIDTH 1100 mm DEPTH 460 mm WEIGHT 160 kg AIRFLOW 1750 CFM 3000M Hr TOTAL POWER 6 0Kw MAX MAXIMUM OPERATING TEMPERATURE 35 C 95 F POWER SUPPLY...

Page 4: ...Remove the front cover b Check the actual relative humidity inside the area c Set humidity control to a LOWER value than the actual relative humidity d After approximately 6 minutes check the compres...

Page 5: ...ng and flooding of the chamber WIRING Connect a suitably fused 3 phase mains power supply to the MAINS T B terminal block inside the electrical box located at the control panel end of the machine DRAI...

Page 6: ...for life and therefore does not need oiling 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the cover The evaporator coil should be evenly frost coated across its surf...

Page 7: ...of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak cau...

Page 8: ...breaker Little or no water extraction 1 Insufficient air movement 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 C...

Page 9: ...5kg Drain Tube 2014315 3 meters 3 8 Copper Tube 3014203 2 meters 1 2 Copper Tube 3014204 2 meters 5 8 Copper Tube 3014205 2 meters Cork Tape 3100223 1 2 Roll Fan Motor 3030140 1 Axial Fan 3010119 1 So...

Page 10: ...ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTI...

Reviews: