4.5 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

4.6 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

4.7 Switching off the device

;

Disconnect the device from the supply voltage at the main switch for
the supply line.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

Item no. 12218-5-9970 · Revision 76115 · Release 2012-03-06 · Page 9 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for A2D250-AI14-10

Page 1: ...ied trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety r...

Page 2: ...wellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emissi...

Page 3: ...tions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that c...

Page 4: ...sures have the unit mm 1 Direction of air flow A 2 Depth of screw max 5 mm 3 Connection line PFA 4G 4x brass lead tips crimped Item no 12218 5 9970 Revision 76115 Release 2012 03 06 Page 4 10 ebm paps...

Page 5: ...ge VAC 480 Connection Y Frequency Hz 60 Type of data definition fa Valid for approval standard CE Speed min 1 2680 Power input W 170 Current draw A 0 23 Max back pressure Pa 110 Min ambient temperatur...

Page 6: ...s that meet the specified installation requirements for voltage current insulation material load etc Route cables such that they cannot be touched by any rotating parts CAUTION Electrical voltage The...

Page 7: ...requency converter only after consultation with ebm papst Fit sinusoidal filters that work on all poles live live and live earth between the frequency inverter and the motor for operation with frequen...

Page 8: ...ion of rotation by reversing two phases Three phase motor Y Star connection L1 black L2 blue L3 brown PE green yellow Item no 12218 5 9970 Revision 76115 Release 2012 03 06 Page 8 10 ebm papst Mulfing...

Page 9: ...ltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION The motor restarts automatically when operating...

Page 10: ...eplacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least...

Reviews: