background image

Operating instructions

A3G560-AP68-35

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

PE

-

PE

Protective earth terminal

KL1

1, 2

N, L

Power supply 50/60 Hz

KL2

1

NC

Floating status contact, break for failure

KL2

2

COM

Floating status contact, changeover contact, common connection
(2 A, max. 250 VAC, min. 10 mA, AC1)

KL2

3

NO

Floating status contact, make for failure

KL3

1

OUT

Analog output, 0-10 VDC, max. 3 mA, SELV
output of current motor modulation level:
1 V corresponds to 10% modulation level.
10 V corresponds to 100% modulation level.

KL3

2, 8

GND

Reference ground for control interface, SELV

KL3

3, 7

0-10 V

Control/current sensor value input 0-10 VDC, impedance 100 kΩ, use only as alternative to 4-20 mA input,
SELV

KL3

4

+10 V

Voltage output 10 VDC (+/- 3%), max. 10 mA,
power supply for ext. devices (e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA
power supply for ext. devices (e.g. sensors), SELV

KL3

6

4-20 mA

Control/current sensor value input 4-20 mA, impedance 100 Ω, use only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for MODBUS, RSB

KL3

10, 12

RSA

RS485 interface for MODBUS, RSA

Item no. 52199-5-9970 · ENU · Change 205846 · Approved 2020-01-22 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for A3G560-AP68-35

Page 1: ...Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety ha...

Page 2: ...contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be eject...

Page 3: ...r operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation wit...

Page 4: ...on of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 3 Max clearance for screw 16 mm 4 Tightening torque 3 5 0 5 Nm Item no 52199 5 9970 ENU Change 205846 Approved 2020 01...

Page 5: ...ency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 8 8 kg Size 560 mm Motor size 112 Rotor surface Painted bl...

Page 6: ...ar the hub Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface Make sure the blades...

Page 7: ...rated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage...

Page 8: ...ed by fitting a cable tie directly in front of the cable gland for example Fans installed upright When routing the cable make sure that the cable glands are located at the bottom The cables must alway...

Page 9: ...ation level KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Control current sensor value input 0 10 VDC impedance 100 k use only as alternative to 4 20 mA input SELV KL3 4 10 V...

Page 10: ...witching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power sup...

Page 11: ...ng If the fans are not treated by the stationary soaking installation in the barn they have to be manually soaked separately using a hosepipe or knapsack sprayer for example Instructions for cleaning...

Page 12: ...lso to be heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into sui...

Reviews: