Operating instructions

A3G630-AD03-A1

Translation of the original operating instructions

4.6 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

4.7 Switch on device

The device is not to be switched on until it has been installed properly
and in accordance with its intended use, including the required protective
devices and professional electrical connection. This also applies to
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

;

Start the device by changing the input signal.

NOTE
Damage to device by vibrations

Bearing damage, reduced service life
→ The fan must operate free of vibrations throughout its speed

control range. #Strong vibrations can result from improper
handling, imbalance resulting from damage during transport,
or component-induced or structural resonances. #When
putting the fan into service, determine the speed ranges with
excessive vibration levels and also any resonance
frequencies that may be present. #When regulating the
speed, pass through resonance ranges as quickly as
possible or find another remedy.# Operation at excessive
vibration levels can lead to premature failure.

4.8 Switching off the device

Switching off the device during operation:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

Switching off the device for maintenance work:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

;

Disconnect the device from the supply voltage.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Line under-voltage (mains input
voltage outside of permitted
nominal voltage)

;

If the mains supply voltage

returns to permitted values, the
motor restarts automatically.

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor will restart automatically, e.g. after power
failure.

Risk of injury
→ Keep out of the device danger zone.# When working on the

device, switch off the mains power and ensure that it cannot
be switched back on.

→ After working on the device, remove any tools used or

other objects from the device.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after cleaning,
replace the device.
If you have
attached any weight
clips during cleaning,
make sure to remove
them afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains supply
voltage,
restore power
supply,
apply control signal.

Item no. 50323-5-9970 · ENG · Revision 89187 · Release 2016-04-14 · Page 10 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for A3G630-AD03-A1

Page 1: ...device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once...

Page 2: ...device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impell...

Page 3: ...device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibration...

Page 4: ...n of air flow V 2 Depth of screw max 10 mm 3 Connection line PVC AWG18 5 x crimped core end sleeve 4 Connection line PVC AWG22 3x crimped core end sleeves Item no 50323 5 9970 ENG Revision 89187 Relea...

Page 5: ...finition with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 8 kg Size 630 mm Surface of rot...

Page 6: ...be damaged Set down the fan carefully on a soft surface Make sure the blades are not subjected to load After installation make sure the impeller moves easily and that the blades of the impeller are n...

Page 7: ...witched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If th...

Page 8: ...th which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value control Analog Control funct...

Page 9: ...connection 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status message contact normally closed connection 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC re...

Page 10: ...ct the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to s...

Page 11: ...sary Visual inspection At least every 6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6...

Page 12: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for internal wiring Electrolytic...

Reviews: