Operating instructions

A3G630-AD03-A1

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1,2

PE

green/
yellow

Protective earth

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, normally closed connection (2 A, max. 250 VAC, min. 10 mA)

1

6

NC

white 2

Floating status message contact, normally closed connection

2

8

0 - 10 V

yellow

Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV

2

11

10 VDC

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50323-5-9970 · ENG · Revision 89187 · Release 2016-04-14 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for A3G630-AD03-A1

Page 1: ...device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once...

Page 2: ...device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impell...

Page 3: ...device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibration...

Page 4: ...n of air flow V 2 Depth of screw max 10 mm 3 Connection line PVC AWG18 5 x crimped core end sleeve 4 Connection line PVC AWG22 3x crimped core end sleeves Item no 50323 5 9970 ENG Revision 89187 Relea...

Page 5: ...finition with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 8 kg Size 630 mm Surface of rot...

Page 6: ...be damaged Set down the fan carefully on a soft surface Make sure the blades are not subjected to load After installation make sure the impeller moves easily and that the blades of the impeller are n...

Page 7: ...witched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If th...

Page 8: ...th which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value control Analog Control funct...

Page 9: ...connection 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status message contact normally closed connection 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC re...

Page 10: ...ct the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to s...

Page 11: ...sary Visual inspection At least every 6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6...

Page 12: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for internal wiring Electrolytic...